EasyManuals Logo

Simplex 4100ES Installation Guide

Simplex 4100ES
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #166 background imageLoading...
Page #166 background image
8-2
Chapter 8 EPS and IDNet 2 Wiring
EPS Wiring Overview
General Wiring
Guidelines
Conductors must test free of all grounds.
All wiring must be done using copper conductors only, unless noted otherwise.
If shielded wire is used:
- the metallic continuity of the shield must be maintained throughout the entire cable
length.
- the entire length of the cable must have a resistance greater than 1 Megohm to
earthground.
Underground wiring must be free of all water.
In areas of high lightning activity, or in areas that have large power surges, the 2081-9027
Transient Suppressor should be used on monitor points.
Wires must not be run through elevator shafts.
Splicing is permitted. All spliced connections must either be soldered (resin-core solder),
crimped in metal sleeves, or encapsulated with an epoxy resin. When soldering or crimped
metal sleeves are used, the junction must be insulated with a high-grade electrical tape that is
as sound as the original insulating jacket. Shield continuity must be maintained throughout.
A system ground must be provided for earth detection and lightning protection devices. This
connection must comply with approved earth detection per NFPA780.
Only system wiring can be run together in the same conduit.
Power-Limited
Guidelines
Non-power limited field wiring (AC power, batteries, City connection) must be installed and
routed in the shaded areas shown in Figure 8-1.
Power-limited field wiring must be installed and routed in the non-shaded shown in Figure
8-1, with the exception of City wiring.Excess slack should be kept to a minimum inside the
back box enclosure. The wiring should be neatly dressed and bundled together using wire
ties. Anchor power-limited wiring to tie points.
Tie the wiring located between bays to the internal wiring troughs, if applicable.
When powering remote units or switching power through relay contacts, power for these
circuits must be provided by a power-limited power supply listed for fire-protective
signaling use.
Figure 8-1. Power-Limited Wiring Guidelines
Conduit Entrance for
Non-Power Limited
Wiring
Conduit Entrance for
Power-Limited Wiring
Non-Power Limited
Wiring (Route in
Shaded Area Only)
Power-Limited Wiring
Tie Point
(Location
May Vary)

Table of Contents

Other manuals for Simplex 4100ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES and is the answer not in the manual?

Simplex 4100ES Specifications

General IconGeneral
TypeFire Alarm Control Panel
DisplayLCD
Battery BackupYes
Model4100ES
ManufacturerSimplex
Communication ProtocolOptional Ethernet
Signaling Line Circuits (SLCs)Up to 10
Notification Appliance Circuits (NACs)Up to 10
Agency ListingsUL, FM, CSFM, MEA
Max Relay Circuits20
Communication PortsEthernet
Operating Temperature32°F to 120°F (0°C to 49°C)
HumidityUp to 93% RH, non-condensing

Related product manuals