EasyManua.ls Logo

Simplex 4100ES - Figure 2-17. Mounting the PDM Bracket (2-Bay Box Shown)

Simplex 4100ES
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-19
Chapter 2 Installing FACP Components
Step 2. Mounting the System Electronics (continued)
Mounting the
System Electronics
Bay
4. Mount the power distribution module (PDM) to the back box as shown in Figure 2-17.
Securely tighten all mounting screws. Refer to Table 2-9 for the recommended torque.
Table 2-9. Recommended Torque for Mounting Hardware
Figure 2-17. Mounting the PDM Bracket (2-Bay Box Shown)
5. If provided, mount the tamper switch assembly to the mounting studs as shown in
Figure 2-17. Refer to 4100-Series Tamper Switch Installation Instructions (579-195).
6. Using the hardware provided with the back box, insert the required number of mounting
screws to the right and left support holes in the back box as shown in Figure 2-18.
7. Tighten the mounting screws.
Note: Install the mounting screws to within 1/8" from the seated position.
Continued on the next page
Screw / Nut Size Recommended Torque
No. 6 7.9 to 8.7 inch/ounces (569 to 626 cm/grams)
No. 8 16.1 to 17.8 inch/ounces (1 159 to 1 282 cm/grams)
No. 10 26.8 to 29.7 inch/ounces (1 930 to 2 139 cm/grams)
PDM
MOUNTING
AREA
TAMPER SWITCH
MOUNTING STUDS
PDM
COVER
Use spacers
to secure
PDM to
cabinet
PDM
CONNECTORS
INSULATOR
CABINET
STANDOFF

Table of Contents

Other manuals for Simplex 4100ES

Related product manuals