B-15
Appendix B
Step 3. Configuring Modules (continued)
565-148 Master
Controller
Configuration
If the 565-148 Master Controller is being used, use the jumper settings described below.
P2. Controls whether RAM battery backup is enabled.
• Position 1 – 2: Enable RAM battery backup.
• Position 2 – 3: Disable RAM battery backup.
P3. Controls whether Flash EPROM writes are enabled.
• Position 1 – 2: Enable Flash EPROM writes.
• Position 2 – 3: Disable Flash EPROM writes.
UPS
Configuration
Note: ON = 0; OFF = 1.
DIP Switch SW1. Controls various UPS functions.
SW1-1. Set to 0. Used when the UPS must be retrofitted to for Intelligent Power Supply
capabilities.
• Position 0: UPS acts like an Intelligent Power Supply in terms of messages sent to and
received from the master controller.
• Position 1: UPS does not use Intelligent Power Supply functionality at all.
SW1-2. Set to 1 unless UPS B-tap is providing power to a 25-Watt Amplifier. Controls
how the amplifier uses the backup battery.
• Position 0: Amplifier switches to battery backup when told to do so by the master
controller.
• Position 1: Amplifier switches to battery backup upon loss of AC power.
SW1-3 through SW1-6. These switches work together to configure the UPS for different
types of batteries (or no batteries at all). Refer to Table B-4 to determine what settings
should be used.
Continued on next page
IMPORTANT: Always configure the UPS as described below.
Table B-4. UPS SW1 Battery Configurations
DIP Switch Position UPS Configuration
34 56
10 01
Lead-acid battery
10 10
No battery charger
11 01
Audio (25 W Amp) and lead-acid battery
11 10
Audio (25 W Amp) without battery charger
10 00
NICAD battery
11 00
Audio (25 W Amp) and NICAD battery