Chapter 1 Introduction to the 4100ES Fire Alarm System
4100ES PIDs (continued)
Basic Control
Panels
(International)
4100-9532 Master Controller 500PTS (2 Loops) - International 743-1038)
(220/230/240VAC 50/60HZ) 2 X 40 Display, CPU Card, Isolated RUI channel, Power
Distribution Interface Board, Power Supply that includes 250 Addressable/Analog Points,
1 Isolated IDNet channel, 189 Addressable TrueAlert Points, 3 Class B IDNAC (127
devices per IDNAC), 24VAux. Power Tap/Simple NAC, 115 Ah Battery Charger (ULC
Listed for charging external 50 Ah batteries) and 9A Total Signal/Card Power, 207 Watts
Notification Appliance Power (9A @ 23V), 54 Watts field wiring power (6V drop, 9A),
System, IDNet and RUI+ Earth Fault Detection, Power Distribution Module, IDNet
(4 X 5) Module.
4100-9533 Master Controller 750PTS (3 Loops)- International (743-1039)
(220/230/240VAC 50/60HZ) 2 X 40 Display, CPU Card, Isolated RUI channel, Power
Distribution Interface Board, Power Supply that includes 250 Addressable/Analog Points,
1 Isolated IDNet channel, 189 Addressable TrueAlert Points, 3 Class B IDNAC (127
devices per IDNAC), 24VAux. Power Tap/Simple NAC, 115 Ah Battery Charger (ULC
Listed for charging external 50 Ah batteries) and 9A Total Signal/Card Power, 207 Watts
Notification Appliance Power (9A @ 23V), 54 Watts field wiring power (6V drop, 9A),
System, IDNet and RUI+ Earth Fault Detection, Power Distribution Module, 2 IDNet
(4 X 5) Modules.
4100-9534 Master Controller 500PTS (5 Loops)- International (743-1040)
(220/230/240VAC 50/60HZ) 2 x 40 Display, CPU Card, Isolated RUI channel, Power
Distribution Interface Board, Power Supply that includes 250 Addressable/Analog Points,
1 Isolated IDNet channel, 189 Addressable TrueAlert Points, 3 Class B IDNAC (127
devices per IDNAC), 24VAux. Power Tap/Simple NAC, 115 Ah Battery Charger (ULC
Listed for charging external 50 Ah batteries) and 9A Total Signal/Card Power, 207 Watts
Notification Appliance Power (9A @ 23V), 54 Watts field wiring power (6V drop, 9A),
System, IDNet and RUI+ Earth Fault Detection, Power Distribution Module, IDNet
Module 250 points (4100-3107).
Transponders This section lists the two transponder cabinets, both of which include an expansion bay with a
power distribution interface (PDI) and a transponder interface card (TIC):
4100-9600 Basic Transponder (742-866). Includes a basic TIC.
4100-9601 Local Mode Transponder (742-867). Includes a local mode TIC.
Remote
Annunciator
4100-9610 Remote Annunciator (742-868). Includes an expansion bay with a power
distribution interface (PDI) and a transponder interface card (TIC).
4100-9611 Remote Annunciator (743-081). Includes an expansion bay with a power
distribution interface (PDI) and a transponder interface card (TIC).

Table of Contents

Other manuals for Simplex 4100ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES and is the answer not in the manual?

Simplex 4100ES Specifications

General IconGeneral
TypeFire Alarm Control Panel
DisplayLCD
Battery BackupYes
Model4100ES
ManufacturerSimplex
Communication ProtocolOptional Ethernet
Signaling Line Circuits (SLCs)Up to 10
Notification Appliance Circuits (NACs)Up to 10
Agency ListingsUL, FM, CSFM, MEA
Max Relay Circuits20
Communication PortsEthernet
Operating Temperature32°F to 120°F (0°C to 49°C)
HumidityUp to 93% RH, non-condensing