10-7
Chapter 10 MNS/ECS Application
Programming and Configuration, Continued
Amber Strobes The 4100ES is compatible with the amber strobes listed below:
• 4906-9205, -9206, -9207 (addressable, visible only, “ALERT” lettering)
• 4906-9107, -9108 (non-addressable, visible only, “ALERT” lettering)
• 4906-9208, -9211 (visible only, with both an amber and a clear lens strobe, respectively
marked “ALERT” and “FIRE”)
Other models of Simplex brand strobes are available with “ALERT” instead of “FIRE”. Refer
to the installation instructions for each power supply for complete lists of compatible
appliances.
MNS Wiring The 4100ES field wiring is “power-limited”, with the exception of AC input, battery and the
City Circuit option module wiring. For MNS, the term “power limited” has been replaced by
the NEC term “class 2”. Wherever this document uses the UL864 term “power limited”, it can
be taken to mean class 2. Any wiring deemed “power limited” for UL864 is deemed “class 2”
for MNS.