11.10 n: Special Adjustment
1006 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
If fast changes in the load cause hunting, increase the setting value in 0.1-unit increments. If you cannot stop
hunting, set n8-51 [Pull-in Current @ Acceleration] to 0% and set n8-54 to 0.00 s, and disable compensation
for voltage errors.
n8-55: Motor to Load Inertia Ratio
No.
(Hex.)
Name Description
Default
(Range)
n8-55
(056E)
Motor to Load Inertia
Ratio
Sets the ratio between motor inertia and machine inertia.
0
(0 - 3)
Adjust this parameter in the these conditions:
If torque and speed response is unsatisfactory, gradually increase the setting.
If motors do not start smoothly, gradually increase the setting.
If the motor stalls during run at constant speed, gradually increase the setting.
If there is vibration or hunting, decrease the setting.
Note:
If the value too low, the drive will detect STPo [Motor Step-Out Detected].
If you use one motor or more than motor at low inertia and the value is too high, there can be vibration in the motor.
0 : Below 1:10
Use this setting in these conditions:
The ratio between the motor inertia and machine inertia is less than 1:10
There are large current ripples
1 : Between 1:10 and 1:30
Use this setting in these conditions:
The ratio between the motor inertia and machine inertia is approximately 1:10 to 1:30
Parameter n8-55 = 0 and the drive detects STPo because of an impact load or sudden acceleration/deceleration.
2 : Between 1:30 and 1:50
Use this setting in these conditions:
The ratio between the motor inertia and machine inertia is approximately 1:30 to 1:50
Parameter n8-55 = 1 and the drive detects STPo because of an impact load or sudden acceleration/deceleration.
3 : Beyond 1:50
Use this setting in these conditions:
The ratio between the motor inertia and machine inertia is more than 1:50
Parameter n8-55 = 2 and the drive detects STPo because of an impact load or sudden acceleration/deceleration.
n8-57: HFI Overlap Selection
No.
(Hex.)
Name Description
Default
(Range)
n8-57
(0574)
HFI Overlap
Selection
Sets the function that detects motor speed with high frequency injection.
0
(0, 1)
Note:
When there is high frequency injection, the motor will make an excitation sound.
When you use Zero Speed Control, set E1-09 [Minimum Output Frequency] = 0.0.
0 : Disabled
Use this setting with SPM motors. The speed control range is approximately 1:20.
When n8-57 = 0, you cannot set E1-09 [Minimum Output Frequency] 1/20 of the value of E1-06 [Base
Frequency].
1 : Enabled
Use this setting with IPM motors. The speed control range changes to 1:100 for very accurate speed detection.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV