11.11 o: Keypad-Related Settings
1014 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Note:
• You can show a maximum of three selected monitors on one LCD keypad screen.
–When you select only one monitor, the text size of this monitor increases. For example, when o1-25 to o1-35 = 0, the text size of the
monitor saved in o1-24 increases.
–When you select two monitors, the text size of these monitors increase.
–When you select four or more monitors, the fourth monitor and all additional monitors are shown on the next screens.
• You can show the monitors that you select with o1-24 to o1-26 as a bar graph, analog gauge, or trend plot.
–Bar graph display: 3 monitors maximum
Select with o1-24, o1-25, and o1-26.
–Analog gauge display: 1 monitor
Select with o1-24.
–Trend plot display: 2 monitors
Select with o1-24 and o1-25.
• You can only set parameters o1-24 to o1-26 with analog output monitors.
• You can set parameters o1-27 to o1-35 with all monitors.
■ o1-36: LCD Backlight Brightness
No.
(Hex.)
Name Description
Default
(Range)
o1-36
(11B9)
RUN
LCD Backlight
Brightness
Sets the intensity of the LCD keypad backlight.
3
(1 - 5)
When you decrease the setting value, the intensity of the backlight decreases. When you increase the setting
value, the intensity of the backlight increases.
■ o1-37: LCD Backlight ON/OFF Selection
No.
(Hex.)
Name Description
Default
(Range)
o1-37
(11BA)
RUN
LCD Backlight ON/
OFF Selection
Sets the automatic shut off function for the LCD backlight.
1
(0, 1)
Note:
Use o1-36 [LCD backlight adjustment] to adjust the intensity of the LCD backlight.
0 : OFF
1 : ON
Enables the automatic shut off function. The time at which the LCD backlight automatically turns off is
configured with o1-38 [Time to turn off LCD backlight].
■ o1-38: LCD Backlight Off-Delay
No.
(Hex.)
Name Description
Default
(Range)
o1-38
(11BB)
RUN
LCD Backlight Off-
Delay
Sets the time until the LCD backlight automatically turns off.
60 s
(10 - 300 s)
When o1-37 = 1 [LCD backlight ON/OFF Selection= ON], the backlight will automatically turn off after the time
set in o1-38 is expired.
When the backlight is off, push a key on the keypad to temporarily turn the backlight on. After the backlight turns
on, it will turn off automatically after the time set in o1-38 is expired.
■ o1-39: Show Initial Setup Screen
No.
(Hex.)
Name Description
Default
(Range)
o1-39
(11BC)
RUN
Show Initial Setup
Screen
Sets the function to show the LCD keypad initial setup screen each time the
drive is energized. This parameter is only available when using an LCD
keypad.
1
(0, 1)