Mechanical & Electrical
Installation
2
2.14 Control Circuit Wiring
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 109
A - Terminal block (TB2-3)
B - Terminal block (TB2-2)
C - Terminal block (TB2-1)
D - Terminal block (TB1)
E - Terminal block (TB3)
F - Terminal block (TB4)
Figure 2.103 Control Circuit Terminal Arrangement
Control Circuit Wire Gauges and Tightening Torques
Use the tables in this section to select the correct wires. Use shielded wire for the control circuit terminal block.
Use crimp ferrules on the wire ends to make wiring easier and more reliable.
Table 2.25 Control Circuit Wire Gauges and Tightening Torques
Terminal
Bare Wire Crimp Ferrule
Recommended
Gauge
mm
2
(AWG)
Applicable Gauge
mm
2
(AWG)
Recommended
Gauge
mm
2
(AWG)
Applicable Gauge
mm
2
(AWG)
S1 - S8, SC, SN, SP
H1, H2, HC
RP, +V, -V, A1, A2, A3, AC
MP, FM, AM, AC
D+, D-, AC
MA, MB, MC, M1-M6
PS, E(G)
0.75
(18)
Stranded wire
0.2 - 1.0
(24 - 18)
Solid wire
0.2 - 1.5
(24 - 16)
0.5
(20)
0.25 - 0.5
(24 - 20)
Crimp Ferrules
Attach an insulated sleeve when you use crimp ferrules. Refer to Table 2.26 for the recommended external
dimensions of the crimp ferrule and the model number.
Use the CRIMPFOX 6, a crimping tool made by PHOENIX CONTACT.
Figure 2.104 External Dimensions of Crimp Ferrules
Table 2.26 Crimp Ferrule Models and Sizes
Wire Gauge
mm
2
(AWG)
Model L (mm) L1 (mm) φd1 (mm) φd2 (mm)
0.25 (24) AI 0.25-8YE 12.5 8 0.8 2.0
0.34 (22) AI 0.34-8TQ 12.5 8 0.8 2.0
0.5 (20)
AI 0.5-8WH,
AI 0.5-8OG
14 8 1.1 2.5