10.17 U: Monitors
612 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
No.
(Hex.)
Name Description
MFAO Signal
Level
Ref.
U6-27
(006D)
Expert
FeedFwd Estimate
Spd
Shows the feed forward estimated speed.
Unit: 0.01%
10 V = Maximum
frequency
(-10 V to +10 V)
-
U6-31
(007B)
TorqueDetect
Monitor
Monitors the torque reference or the output current after applying
the filter set to L6-07 [Torque Detection Filter Time].
Unit: 0.1%
10 V:100% -
U6-36
(0720)
Expert
Comm Errors-Host
Shows the number of inter-CPU communication errors. De-
energizing the drive sets this number to 0.
No signal output
available
-
U6-37
(0721)
Expert
Comm Errors-
Sensor
Shows the number of inter-CPU communication errors. De-
energizing the drive sets this number to 0.
No signal output
available
-
U6-48
(072E)
Expert
ASIC Comm
Errors
Counts the number of inter-ASIC communication errors detected by
the ASIC. This count is reset to 0 when the power to the drive is
turned off.
No signal output
available
-
U6-57
(07C4)
PolePolarityDeterV
al
Shows the change from the integrated current when finding the
polarity.
Unit: 1
Note:
If the change from the integrated current is less than 819,
increase n8-84 [Polarity Detection Current]. U6-57 = 8192 is
equivalentto the motor rated current.
No signal output
available
-
U6-80 to
U6-83
(07B0 to
07B3)
Option IP Address
1 to 4
Shows the currently available local IP Address.
• U6-80: 1st octet
• U6-81: 2nd octet
• U6-82: 3rd octet
• U6-83: 4th octet
No signal output
available
-
U6-84 to
U6-87
(07B4 to
07B7)
Online Subnets 1
to 4
Shows the currently available subnet mask.
• U6-84: 1st octet
• U6-85: 2nd octet
• U6-86: 3rd octet
• U6-87: 4th octet
No signal output
available
-
U6-88 to
U6-91
(07B8,
07B9, 07F0,
07F1)
Online Gateways 1
to 4
Shows the currently available gateway address.
• U6-88: 1st octet
• U6-89: 2nd octet
• U6-90: 3rd octet
• U6-91: 4th octet
No signal output
available
-
U6-92
(07F2)
Online Speed
Shows the currently available communications speed.
10: 10 Mbps
100: 100 Mbps
No signal output
available
-
U6-93
(07F3)
Online Duplex
Shows the currently available Duplex setting.
No signal output
available
-
U6-98
(07F8)
First Fault
Shows the contents of the most recent communication options fault
(DeviceNet, Modbus TCP/IP, EtherNet/IP).
No signal output
available
-
U6-99
(07F9)
Current Fault
Shows the contents of current fault from communication options
(DeviceNet, Modbus TCP/IP, EtherNet/IP).
No signal output
available
-