Parameter List
10
10.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 627
No.
*1
Name Unit Default
-
Drive
Model
- 2042 2056 2070 2082
C6-01
Normal /
Heavy
Duty
Selection
-
HD (ND) HD (ND) HD (ND) HD (ND)
0 1 0 1 0 1 0 1
o2-04
Drive
Model
(KVA)
Selection
Hex. 6B 6D 6E 6F
E2-11
(E4-11)
Motor
Rated
Power
(kW)
kW 7.5 11 11 15 15 18.5 18.5 22
b3-04
V/f Gain
during
Speed
Search
% 100 100 100 100 100 100 100 100
b3-06
Speed
Estimation
Current
Level 1
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Speed
Estimation
ACR P
Gain
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-26
Direction
Determina
tion Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
Energy
Saving
Filter Time
s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b8-04
Energy
Saving
Coefficient
Value
- 72.69 70.44 70.44 63.13 63.13 57.87 57.87 51.79
C5-17
(C5-37)
Motor
Inertia
kgm
2
0.037 0.053 0.053 0.076 0.076 0.138 0.138 0.165
C6-02
Carrier
Frequency
Selection
- 1 7 1 7 1 7 1 7
E2-01
(E4-01)
Motor
Rated
Current
(FLA)
A 26.6 39.7 39.7 53 53 65.8 65.8 77.2
E2-02
(E4-02)
Motor
Rated Slip
Hz 1.3 1.7 1.7 1.6 1.6 1.67 1.67 1.7
E2-03
(E4-03)
Motor No-
Load
Current
A 8 11.2 11.2 15.2 15.2 15.7 15.7 18.5
E2-05
(E4-05)
Motor
Line-to-
Line
Resistance
Ω 0.288 0.23 0.23 0.138 0.138 0.101 0.101 0.079
E2-06
(E4-06)
Motor
Leakage
Inductance
% 15.5 19.5 19.5 17.2 17.2 15.7 20.1 19.5
E2-10
(E4-10)
Motor Iron
Loss
W 262 245 245 272 272 505 505 538
E5-01
PM Motor
Code
Selection
- 120B 120B 120D 120D 120E 120E 120F 120F