10.21 Defaults by Drive Model and Duty Rating ND/HD
626 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
No.
*1
Name Unit Default
-
Drive
Model
- 2012 2018 2021 2030
C6-01
Normal /
Heavy
Duty
Selection
-
HD (ND) HD1 ND1 HD1 ND1 HD (ND)
0 1 0 1 0 1 0 1
o2-04
Drive
Model
(KVA)
Selection
Hex. 66 67 68 6A
E2-11
(E4-11)
Motor
Rated
Power
(kW)
kW 2.2 3.0 3.0 3.7 3.7 5.5 5.5 7.5
L2-02
Power
Loss Ride
Through
Time
s 0.5 0.5 1 1 1 1 1 1
L2-03
Minimum
Baseblock
Time
s 0.5 0.5 0.5 0.6 0.6 0.7 0.7 0.8
L2-04
Powerloss
V/f
Recovery
Ramp
Time
s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
L2-05
Undervolt
age
Detection
Lvl (Uv1)
- 190 190 190 190 190 190 190 190
L3-24
Motor
Accel
Time @
Rated
Torque
s 0.145 0.145 0.145 0.154 0.154 0.168 0.168 0.175
L8-02
Overheat
Alarm
Level
°C 124 124 110 110 110 110 110 110
L8-09
Output
Ground
Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 1 1 1 1 1 1 1 1
n1-03
Hunting
Prevention
Time
Constant
ms 10 10 10 10 10 10 10 10
n1-16
Hunting
Prevention
High Fc
Gain
- 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
n5-02
Motor
Inertia
Accelera
tion Time
s 0.145 0.145 0.145 0.154 0.154 0.168 0.168 0.175
n8-11
Observer
Calculation
Gain 2
- 30.0 30.0 30.0 30.0 30.0 30.0 30.0 30.0
*1 Parameters within parentheses are for motor 2.