Parameter List
10
10.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 637
No.
*1
Name Unit Default
-
Drive
Model
- 4031 4038 4044 4060
C6-01
Normal /
Heavy
Duty
Selection
-
HD1 ND1 HD1 ND1 HD1 ND1 HD1 ND1
0 1 0 1 0 1 0 1
o2-04
Drive
Model
(KVA)
Selection
Hex. 9C 9D 9E 9F
E2-11
(E4-11)
Motor
Rated
Power
(kW)
kW 11 15 15 18.5 18.5 22 22 30
b3-04
V/f Gain
during
Speed
Search
% 100 100 100 100 100 100 100 100
b3-06
Speed
Estimation
Current
Level 1
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Speed
Estimation
ACR P
Gain
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-26
Direction
Determina
tion Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
Energy
Saving
Filter Time
s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b8-04
Energy
Saving
Coefficient
Value
- 140.88 126.26 126.26 115.74 115.74 103.58 103.58 92.54
C5-17
(C5-37)
Motor
Inertia
kgm
2
0.053 0.076 0.076 0.138 0.138 0.165 0.165 0.220
C6-02
Carrier
Frequency
Selection
- 1 7 1 7 1 7 1 7
E2-01
(E4-01)
Motor
Rated
Current
(FLA)
A 19.9 26.5 26.5 32.9 32.9 38.6 38.6 52.3
E2-02
(E4-02)
Motor
Rated Slip
Hz 1.7 1.6 1.6 1.67 1.67 1.7 1.7 1.8
E2-03
(E4-03)
Motor No-
Load
Current
A 5.6 7.6 7.6 7.8 7.8 9.2 9.2 10.9
E2-05
(E4-05)
Motor
Line-to-
Line
Resistance
Ω 0.922 0.55 0.55 0.403 0.403 0.316 0.316 0.269
E2-06
(E4-06)
Motor
Leakage
Inductance
% 19.6 17.2 17.2 20.1 20.1 23.5 23.5 20.7
E2-10
(E4-10)
Motor Iron
Loss
W 385 440 440 508 508 586 586 750
E5-01
PM Motor
Code
Selection
- 123D 123D 123E 123E 123F 123F 1240 1240