10.21 Defaults by Drive Model and Duty Rating ND/HD
638 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
No.
*1
Name Unit Default
-
Drive
Model
- 4031 4038 4044 4060
C6-01
Normal /
Heavy
Duty
Selection
-
HD1 ND1 HD1 ND1 HD1 ND1 HD1 ND1
0 1 0 1 0 1 0 1
o2-04
Drive
Model
(KVA)
Selection
Hex. 9C 9D 9E 9F
E2-11
(E4-11)
Motor
Rated
Power
(kW)
kW 11 15 15 18.5 18.5 22 22 30
L2-02
Power
Loss Ride
Through
Time
s 2 2 2 2 2 2 2 2
L2-03
Minimum
Baseblock
Time
s 0.9 1 1 1 1 1 1 1.1
L2-04
Powerloss
V/f
Recovery
Ramp
Time
s 0.3 0.6 0.6 0.6 0.6 0.6 0.6 0.6
L2-05
Undervolt
age
Detection
Lvl (Uv1)
- 380 380 380 380 380 380 380 380
L3-24
Motor
Accel
Time @
Rated
Torque
s 0.265 0.244 0.244 0.317 0.317 0.355 0.355 0.323
L8-02
Overheat
Alarm
Level
°C 100 100 120 120 120 120 130 137
L8-09
Output
Ground
Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 2 2 2 2 2 2 2 2
n1-03
Hunting
Prevention
Time
Constant
ms 10 10 10 10 10 10 10 10
n1-16
Hunting
Prevention
High Fc
Gain
- 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
n5-02
Motor
Inertia
Accelera
tion Time
s 0.265 0.244 0.244 0.317 0.317 0.355 0.355 0.323
n8-11
Observer
Calculation
Gain 2
- 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0
*1 Parameters within parentheses are for motor 2.