Parameter List
10
10.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 643
No.
*1
Name Unit Default
-
Drive
Model
- 4371 4389 4453 4568
C6-01
Normal /
Heavy
Duty
Selection
-
HD1 ND1 HD1 ND1 HD1 ND1 HD1 ND1
0 1 0 1 0 1 0 1
o2-04
Drive
Model
(KVA)
Selection
Hex. A9 AA AF AD
E2-11
(E4-11)
Motor
Rated
Power
(kW)
kW 160 200 200 220 220 250 250 315
b3-04
V/f Gain
during
Speed
Search
% 60 60 60 60 60 60 60 60
b3-06
Speed
Estimation
Current
Level 1
- 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
b3-08
Speed
Estimation
ACR P
Gain
- 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
b3-26
Direction
Determina
tion Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
Energy
Saving
Filter Time
s 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00
b8-04
Energy
Saving
Coefficient
Value
- 30.13 30.57 30.57 27.13 27.13 21.76 21.76 21.76
C5-17
(C5-37)
Motor
Inertia
kgm
2
3.30 3.60 3.60 4.10 4.10 6.50 6.50 11.00
C6-02
Carrier
Frequency
Selection
- 1 7 1 7 1 7 1 7
E2-01
(E4-01)
Motor
Rated
Current
(FLA)
A 270 310 310 370 370 500 500 500
E2-02
(E4-02)
Motor
Rated Slip
Hz 1.35 1.3 1.3 1.3 1.3 1.25 1.25 1.25
E2-03
(E4-03)
Motor No-
Load
Current
A 70 81 81 96 96 130 130 130
E2-05
(E4-05)
Motor
Line-to-
Line
Resistance
Ω 0.029 0.025 0.025 0.02 0.02 0.014 0.014 0.014
E2-06
(E4-06)
Motor
Leakage
Inductance
% 20 20 20 20 20 20 20 20
E2-10
(E4-10)
Motor Iron
Loss
W 2850 3200 3200 3700 3700 4700 4700 4700
E5-01
PM Motor
Code
Selection
- 124A 124A 124A 124A 124A 124A 124A 124A