10.21 Defaults by Drive Model and Duty Rating ND/HD
644 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
No.
*1
Name Unit Default
-
Drive
Model
- 4371 4389 4453 4568
C6-01
Normal /
Heavy
Duty
Selection
-
HD1 ND1 HD1 ND1 HD1 ND1 HD1 ND1
0 1 0 1 0 1 0 1
o2-04
Drive
Model
(KVA)
Selection
Hex. A9 AA AF AD
E2-11
(E4-11)
Motor
Rated
Power
(kW)
kW 160 200 200 220 220 250 250 315
L2-02
Power
Loss Ride
Through
Time
s 2 2 2 2 2 2 2 2
L2-03
Minimum
Baseblock
Time
s 1.8 1.9 1.9 2 2 2.1 2.1 2.1
L2-04
Powerloss
V/f
Recovery
Ramp
Time
s 1 1 1.8 1.8 1.8 2 2 2
L2-05
Undervolt
age
Detection
Lvl (Uv1)
- 380 380 380 380 380 380 380 380
L3-24
Motor
Accel
Time @
Rated
Torque
s 0.777 0.864 0.864 0.91 0.91 1.392 1.392 1.392
L8-02
Overheat
Alarm
Level
°C 130 130 140 140 140 140 140 140
L8-09
Output
Ground
Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 2 2 2 2 2 2 2 2
n1-03
Hunting
Prevention
Time
Constant
ms 30 30 100 100 100 100 100 100
n1-16
Hunting
Prevention
High Fc
Gain
- 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
n5-02
Motor
Inertia
Accelera
tion Time
s 0.777 0.864 0.864 0.91 0.91 1.392 1.392 1.392
n8-11
Observer
Calculation
Gain 2
- 50.0 50.0 50.0 50.0 50.0 50.0 50.0 50.0