EasyManua.ls Logo

YASKAWA GA700 - Page 671

YASKAWA GA700
1053 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter List
10
10.22 Parameters Changed by PM Motor Code Selection
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 671
No. Name Unit Motor Code (setting value of E5-01)
n5-02
Motor
Acceleration Time
s 0.080 0.081 0.078 0.088 0.066 0.070 0.085
n8-49
d-Axis Cur
forHighEfficiency
Cont
% -8.4 -11.0 -9.9 -9.0 -11.4 -23.2 -22.1
*1 Default settings vary depending on the setting of o2-04 (Drive Model Selection).
Table 10.34 SST4 Series Motor Code Setting for Specification of 400 V at 1150 min
-1
(r/min)
No. Name Unit Motor Code (setting value of E5-01)
E5-01
PM Motor Code
Selection
- 243D 243E 243F 2440 2442 2443 2444
Voltage Class V 400 400 400 400 400 400 400
Capacity kW 11 15 18 22 30 37 45
Motor Rotation
Speed
min
-1
1150 1150 1150 1150 1150 1150 1150
E5-02
PM Motor Rated
Power (kW)
kW 11.0 15 18.50 22.00 30.00 37.00 45.00
E5-03
PM Motor Rated
Current (FLA)
A 19.5 27.7 32.7 39.2 51.8 63.0 76.6
E5-04
PM Motor Pole
Count
- 6 6 6 6 6 6 6
E5-05
PM Motor
Resistance (ohms/
phase)
Ω 0.460 0.325 0.260 0.209 0.140 0.106 0.076
E5-06
PM d-axis
Inductance (mH/
phase)
mH 17.76 12.83 11.68 10.09 8.12 6.43 4.96
E5-07
PM q-axis
Inductance (mH/
phase)
mH 22.72 17.19 15.16 16.25 9.84 7.71 6.56
E5-09
PM Back-EMF
Vpeak (mV/(rad/
s))
mVs/rad 740.4 716.6 809.1 786.2 888.8 857.7 941.6
E5-24
PM Motor Induced
Voltage Constant 2
(Ke)
mV/(r/
min)
0.0 0.0 0.0 0.0 0.0 0.0 0.0
E1-04
Maximum Output
Frequency
Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5
E1-05
Maximum Output
Voltage
V 380.0 380.0 380.0 380.0 380.0 380.0 380.0
E1-06 Base Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5
E1-09
Minimum Output
Frequency
Hz 2.9 2.9 2.9 2.9 2.9 2.9 2.9
C5-17 Motor Inertia kgm
2
0.054 0.063 0.113 0.137 0.252 0.304 0.410
L3-24
*1
Motor Accel Time
for Inertia Cal
s 0.071 0.061 0.089 0.090 0.122 0.119 0.132
n5-02
Motor
Acceleration Time
s 0.071 0.061 0.089 0.090 0.122 0.119 0.132
n8-49
d-Axis Cur
forHighEfficiency
Cont
% -16.7 -20.2 -15.2 -27.7 -9.8 -10.2 -11.5
*1 Default settings vary depending on the setting of o2-04 (Drive Model Selection).

Table of Contents

Other manuals for YASKAWA GA700

Related product manuals