10.22 Parameters Changed by PM Motor Code Selection
672 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Table 10.35 SST4 Series Motor Code Setting for Specification of 400 V at 1150 min
-1
(r/min)
No. Name Unit Motor Code (setting value of E5-01)
E5-01
PM Motor Code
Selection
- 2445 2446 2447 2448 2449 244A 244C
Voltage Class V 400 400 400 400 400 400 400
Capacity kW 55 75 90 110 132 160 200
Motor Rotation
Speed
min
-1
1150 1150 1150 1150 1150 1150 1150
E5-02
PM Motor Rated
Power (kW)
kW 55.00 75.00 90.00 110.00 132.00 160.00 200.00
E5-03
PM Motor Rated
Current (FLA)
A 93.1 128.1 153.1 186.5 221.9 269.8 336.5
E5-04
PM Motor Pole
Count
- 6 6 6 6 6 6 6
E5-05
PM Motor
Resistance (ohms/
phase)
Ω 0.051 0.032 0.026 0.015 0.012 0.009 0.007
E5-06
PM d-axis
Inductance (mH/
phase)
mH 3.99 2.97 2.44 1.87 1.49 1.41 1.22
E5-07
PM q-axis
Inductance (mH/
phase)
mH 5.39 3.90 3.23 2.46 2.08 1.88 1.51
E5-09
PM Back-EMF
Vpeak (mV/(rad/
s))
mVs/rad 853.8 829.6 835.6 833.4 848.6 889.1 915.0
E5-24
PM Motor Induced
Voltage Constant 2
(Ke)
mV/(r/
min)
0.0 0.0 0.0 0.0 0.0 0.0 0.0
E1-04
Maximum Output
Frequency
Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5
E1-05
Maximum Output
Voltage
V 380.0 380.0 380.0 380.0 380.0 380.0 380.0
E1-06 Base Frequency Hz 57.5 57.5 57.5 57.5 57.5 57.5 57.5
E1-09
Minimum Output
Frequency
Hz 2.9 2.9 2.9 2.9 2.9 2.9 2.9
C5-17 Motor Inertia kgm
2
0.55 0.82 0.96 1.60 1.95 2.82 3.70
L3-24
*1
Motor Accel Time
for Inertia Cal
s 0.145 0.159 0.155 0.211 0.214 0.256 0.268
n5-02
Motor
Acceleration Time
s 0.145 0.159 0.155 0.211 0.214 0.256 0.268
n8-49
d-Axis Cur
forHighEfficiency
Cont
% -15.9 -15.7 -15.7 -14.7 -16.5 -14.1 -10.3
*1 Default settings vary depending on the setting of o2-04 [Drive Model Selection].