Parameter Details
11
11.2 A: Initialization Parameters
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 687
Set the sequence to open the holding brake when you enter an increase or decrease command.
Figure 11.2 Sequence Circuit Configuration Diagram
*1 L4-07 = 0 [Speed Agree Detection Selection = No Detection during Baseblock] or During Frequency Output
Time Chart
Figure 11.3 shows the open/close sequence of the holding brake.
Figure 11.3 Holding Brake Open and Close Sequence Time Chart (V/f, CL-V/f, OLV)
*1 Start braking from the higher set frequency between b2-01 [DC Injection/Zero SpeedThreshold] or E1-09
[Minimum Output Frequency].
Figure 11.4 Holding Brake Open and Close Sequence Time Chart (CLV, CLV/PM)
*1 Start braking from the higher set frequency between b2-01 [DC Injection/Zero SpeedThreshold] or E1-09
[Minimum Output Frequency].