The drive responds more slowly than when it reads the sequence one time, but this setting prevents electrical
interference problems.
■ b1-07: LOCAL/REMOTE Run Selection
No.
(Hex.)
Name Description
Default
(Range)
b1-07
(0186)
LOCAL/REMOTE
Run Selection
Sets drive response to an existing Run command when the drive receives a
second Run command from a different location.
0
(0, 1)
This parameter interlocks the drive to help prevent accidents that can occur if the motor starts to rotate because the
Run command source changed.
To switch the RUN command source, push on the keypad or set H1-xx = 1, 2 [MFDI Function Select =
LOCAL/REMOTE Selection, External Reference 1/2 Selection] and turn the terminal ON/OFF.
0 : Disregard Existing RUN Command
If a Run command is enabled when you switch between Run command sources, the drive will not operate the
motor.
When the drive is operating the motor, turn OFF the Run command to stop the motor. Enter the Run command
again to start operation.
1 : Accept Existing RUN Command
If a Run command is enabled when you switch between Run command sources, the drive will start to operate the
motor or continue to operate the motor.
WARNING! Sudden Movement Hazard.
When using a 3-Wire sequence:
• Set the drive for 3-Wire sequence.
• Set b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command]
• Wire the drive for 3-Wire sequence.
If these three conditions are correct, the motor can rotate in reverse when energizing the drive:
• The drive is wired for 3-Wire sequence.
• The drive is set for a 2-Wire sequence (default).
• b1-17 = 1 [Accept Existing RUN Command]
Failure to obey can cause death or serious injury from moving equipment.
■ b1-08: Run Command Select in PRG Mode
No.
(Hex.)
Name Description
Default
(Range)
b1-08
(0187)
Run Command Select
in PRG Mode
Sets the conditions for the drive to accept a Run command entered from an
external source when using the keypad to set parameters.
0
(0 - 2)
As a safety precaution, when the drive is in Programming Mode, it will not respond to a Run command.
This parameter helps prevent accidents that can occur if the motor starts to rotate because the drive received a Run
command from an external source while the user is programming the drive. You can also set the drive to not show
the Programming Mode when a Run command is active.
Note:
Refer to this table for Drive Mode and Programming Mode functions.
Mode Keypad Screen Function
Drive Mode Monitors Sets monitor display.
Programming
Mode
Parameters Changes parameter settings.
User Custom Parameters Shows the User Parameters.
Parameter Backup/Restore Saves parameters to the keypad as backup.
Modified Parameters/Fault Log Shows modified parameters and fault history.
Auto-Tuning Auto-Tunes the drive.
Initial Setup Changes initial settings.
Diagnostic Tools Sets data logs and backlight.
0 : Disregard RUN while Programming