11.3 b: Application
706 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
The drive rejects the Run command while in Programming Mode.
1 : Accept RUN while Programming
The drive accepts a Run command entered from an external source while in Programming Mode.
2 : Allow Programming Only at Stop
The drive does not let the user enter Programming Mode when the drive is operating. The drive does not show the
Programming Mode when a Run command is active.
b1-14: Phase Order Selection
No.
(Hex.)
Name Description
Default
(Range)
b1-14
(01C3)
Phase Order
Selection
Sets the phase order for output terminals U/T1, V/T2, and W/T3. This
parameter can align the Forward Run command from the drive and the
forward direction of the motor without changing wiring.
0
(0, 1)
0 : Standard
1 : Switch Phase Order
b1-15: Frequency Reference Selection 2
No.
(Hex.)
Name Description
Default
(Range)
b1-15
(01C4)
Frequency Reference
Selection 2
Sets the input method for frequency reference 2.
0
(0 - 4)
This parameter is enabled when H1-xx = 2 [MFDI Function Select = External Reference 1/2 Selection] is
activated.
Note:
Push on the keypad to set the input mode to LOCAL and enter the frequency reference from the keypad.
When the drive receives a Run command when the frequency reference is 0 Hz or less than the E1-09 [Minimum Output Frequency]
value, the on the keypad will flash. Check the setting for the frequency reference input and enter a value more than or equal to the
E1-09 value.
0 : Keypad
Use the keypad to enter the frequency reference.
Use and on the keypad to change the frequency reference.
1 : Analog Input
Use MFAI terminals A1, A2, and A3 to input an analog frequency reference with a voltage or current input signal.
Voltage Input
Refer to Table 11.24 to use a voltage signal input to one of the MFAI terminals.
Table 11.24 Frequency Reference Voltage Input
Terminal
Terminal Signal
Level
Parameter Settings
Note
Signal Level
Selection
Function
Selection
Gain Bias
A1 0 - 10 V H3-01 = 0 H3-02 = 0
[Frequency Bias]
H3-03 H3-04 Set DIP switch
S1-1 to V for
voltage input.
-10 - +10 V H3-01 = 1
A2 0 - 10 V H3-09 = 0 H3-10 = 0
[Frequency Bias]
H3-11 H3-12 Set DIP switch
S1-2 to V for
voltage input.
-10 - +10 V H3-09 = 1
A3 0 - 10 V H3-05 = 0 H3-06 = 0
[Frequency Bias]
H3-07 H3-08 Set DIP switch
S1-3 to V for
voltage input.
Set DIP switch S4
to AI for analog
input.
-10 - +10 V H3-05 = 1
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV