Parameter Details
11
11.8 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 863
Setting Function
47 Node Setup (CANopen)
60 DC Injection Braking Command
61 Speed Search from Fmax
62 Speed Search from Fref
63 Field Weakening
65
*1
KEB Ride-Thru 1 Activate (N.C.)
66
*1
KEB Ride-Thru 1 Activate (N.O.)
67 Communications Test Mode
68 High Slip Braking (HSB) Activate
6A Drive Enable
71 Torque Control
72 Zero Servo
75 Up 2 Command
76 Down 2 Command
Setting Function
77 ASR Gain (C5-03) Select
78 Analog TorqueRef Polarity Invert
7A
*1
KEB Ride-Thru 2 Activate (N.C.)
7B
*1
KEB Ride-Thru 2 Activate (N.O.)
7C
*1
Short Circuit Braking (N.O.)
7D
*1
Short Circuit Braking (N.C.)
7E Reverse Rotation Identifier
7F PID Bi-Directional Enable
90 to 97
*1
DWEZ Digital Inputs 1 to 8
9F DWEZ Disable
101 to 19F Inverse input of 1 to 9F
Does an inverse input on the function of the
selected MFDI. To select the function for
inverse input, enter two digits 01 to 9F for
the “xx” in ”1xx”.
*1 Inverse input is not available.
■ H1-01: Terminal S1 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H1-01
(0438)
Terminal S1 Function
Selection
Sets the function for MFDI terminal S1.
40
(1-19F)
Note:
The default setting is F when the drive is initialized for 3-Wire Initialization [A1-03 = 3330].
■ H1-02: Terminal S2 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H1-02
(0439)
Terminal S2 Function
Selection
Sets the function for MFDI terminal S2.
41
(1 - 19F)
Note:
The default setting is F when the drive is initialized for 3-Wire Initialization [A1-03 = 3330].
■ H1-03: Terminal S3 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H1-03
(0400)
Terminal S3 Function
Selection
Sets the function for MFDI terminal S3.
24
(0 - 19F)
■ H1-04: Terminal S4 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
H1-04
(0401)
Terminal S4 Function
Selection
Sets the function for MFDI terminal S4.
14