11.8 H: Terminal Functions
878 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
3E: PID Setpoint Selection 1
Setting Function Description
3E PID Setpoint
Selection 1
Set this function and H1-xx = 3F [PID Setpoint Selection 2] together. Sets the function to switch
the PID setpoint to b5-58 to b5-60 [PID Setpoint 2 to 4].
Refer to b5-58 to b5-60: PID Setpoint 2 to 4 for more information.
3F: PID Setpoint Selection 2
Setting Function Description
3F PID Setpoint
Selection 2
Set this function and H1-xx = 3E [PID Setpoint Selection 1] together. Sets the function to switch
the PID setpoint to b5-58 to b5-60 [PID Setpoint 2 to 4].
Refer to b5-58 to b5-60: PID Setpoint 2 to 4 for more information.
40: Forward RUN (2-Wire)
Setting Function Description
40 Forward RUN (2-
Wire)
Sets the Forward Run command for 2-wire sequence 1. Set this function and H1-xx = 41 [Reverse
Run Command (2-Wire Seq)] together.
ON : Forward Run
OFF : Run Stop
Note:
Turning ON the Forward Run command terminal and the Reverse Run command terminal will cause alarm EF [FWD/REV Run
Command Input Error] and the motor will ramp to stop.
Initialize the drive with a 2-wire sequence to set the Forward Run command to terminal S1.
This function will not operate at the same time as H1-xx = 42, 43 [Run Command/FWD/REV Command (2-Wire Seq 2)].
Figure 11.86 2-Wire Sequence Wiring Example
41: Reverse RUN (2-Wire)
Setting Function Description
41 Reverse RUN (2-
Wire)
Sets the Reverse Run command for 2-wire sequence 1. Set this function and H1-xx = 40 [Forward
Run Command (2-Wire Seq)] together.
ON : Reverse Run
OFF : Run Stop
Note:
Turning ON the Forward Run command terminal and the Reverse Run command terminal will cause alarm EF [FWD/REV Run
Command Input Error] and the motor will ramp to stop.
Initialize the drive with a 2-wire sequence to set the Reverse Run command to terminal S2.
This function will not operate at the same time as H1-xx = 42, 43 [Run Command/FWD/REV Command (2-Wire Seq 2)].
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV