Parameter Details
11
11.8 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 879
■ 42: Run Command (2-Wire Sequence 2)
Setting Function Description
42 Run Command (2-
Wire Sequence 2)
Sets the Run command for 2-wire sequence 2. Set this function and H1-xx = 43 [FWD/REV
Command (2-Wire Seq 2)] together.
ON : Run
OFF : Stop
Note:
This function will not operate at the same time as H1-xx = 40, 41 [Forward/Reverse Run Command (2-Wire Seq)].
■ 43: FWD/REV (2-Wire Sequence 2)
Setting Function Description
43 FWD/REV (2-Wire
Sequence 2)
Sets the direction of motor rotation for 2-wire sequence 2. Set this function and H1-xx = 42 [Run
Command (2-Wire Sequence 2)] together.
ON : Reverse
OFF : Forward
Note:
• You must input the Run command to rotate the motor.
• This function will not operate at the same time as H1-xx = 40, 41 [Forward/Reverse Run Command (2-Wire Seq)].
■ 44: Add Offset Frequency 1 (d7-01)
Setting Function Description
44 Add Offset
Frequency 1 (d7-01)
Sets the function to add the offset frequency set in d7-01 [Offset Frequency 1] to the frequency
reference when the terminal activates.
Note:
Refer to “d7: Offset Frequency” for more information.
■ 45: Add Offset Frequency 2 (d7-02)
Setting Function Description
45 Add Offset
Frequency 2 (d7-02)
Sets the function to add the offset frequency set in d7-02 [Offset Frequency 2] to the frequency
reference when the terminal activates.
Note:
Refer to “d7: Offset Frequency” for more information.
■ 46: Add Offset Frequency 3 (d7-03)
Setting Function Description
46 Add Offset
Frequency 3 (d7-03)
Sets the function to add the offset frequency set in d7-03 [Offset Frequency 3] to the frequency
reference when the terminal activates.
Note:
Refer to “d7: Offset Frequency” for more information.
■ 47: Node Setup (CANopen)
Setting Function Description
47 Node Setup
(CANopen)
Sets the function in CANopen communications to start the Node Setup function to set the drive
node address from the host controller.