"Z1 Line Leakage Error", where Z1 can be any zone.
o A text message displays at the [Machine Fault Record] window in Ateis Studio, see the
picture as below.
A buzzing sound will be outputted to the monitoring speaker on the front panel of the IDA8C.
Fault Handling : Amplifier Line Leakage Error
Troubleshooting:
1. Plug out the LINE A speaker line, and wait for 90 seconds to check if the Leakage fault has
cleared out or still exists.
2. If there's no Leakage fault, check if the + speaker line is connected to ground wire, and - is
connected ground wire.
7.1.7 EVAC Intput Error
The voltage of EVAC input is not in the range (when the evacuation input is set to "contact mode").
Indication:
LED Indicator: When this error is detected, the following LEDs will light up:
o G. Fault LED on the front panel of the IDA8C/S.
Log:
o EVAC Input Error (OPEN)
"EVAC Input Error" messages will be displayed on the touch screen of the IDA8C.
o A text message will be displayed at the [Machine Fault Record] window in Ateis Studio,