LOG item
Description
(where n = source channel, xxx = zone number)
Paging Stop Source : n At : xxx
(where n = source channel, xxx = zone number)
Paging stop status
URGP 32I Port:m Fault CH:n, Deactive
URGP 32I Port:m Fault CH:n, Active
URGP 32I Port:m CH:n Line Open
URGP 32I Port:m CH:n Short Circuit
(m = 1~4, n = 1~32)
URGP 32I device monitor status
URGP16I16O Port:m ID:1 Fault CH:n, Deactive
URGP16I16O Port:m ID:1 Fault CH:n, Active
URGP16I16O Port:m ID:1 CH:n Line Open
URGP16I16O Port:m ID:1 CH:n Short Circuit
(where m = 1~4, n = 1~16)
URGP16I16O device board monitor status
S/WDOG RETS = xxx
(where xxx = code address)
Watchdog status
Exception RETX= xxx
(where xxx = code address)
Exception status
KernelPanic Code = xxx
(where xxx = code address)
Kernel panic status
File xxx Corruption
(where xxx = file name)
File CRC code error
mmm Audio RMS = nnn
(where mmm = Fireman or PDC, nnn = RMS
value)
Audio RMS value
Major Fault : xxx
(where xxx = user customer define word)
Major fault occurs form the "Fault Definer Security"
Minor Fault : xxx
(where xxx = user customer define word)
Minor fault occurs form the "Fault Definer Security"
Modan Port:n Online
Modan Port:n Offline
(n = 1~65535)
Modan client status
ZB m Zone n Reference_Full_Load-tolerance is
xxx
(where m = 1~2, n = 1~8, xxx = tolerance value)
Zone full load tolerance value recording
ZB m Zone n Reference_Unload+tolerance isxxx
(where m = 1~2, n = 1~8, xxx = tolerance value)
Zone unload tolerance value recording
ZB m Zone n Measure on Full_Load is xxx
(where m = 1~2, n = 1~8, xxx = measure value)
Zone measure value recording
ZB m Zone n Impedance_Reference_AB-
tolerance is xxx (where m = 1~2, n = 1~8, xxx =
reference value)
Zone reference value recording
ZB m Zone n
Impedance_Reference_AB+tolerance is xxx
(where m = 1~2, n = 1~8, xxx = reference value)
Zone reference value recording
ZB m Zone n Impedance Measure on Line AB is
xxx
(where m = 1~2, n = 1~8, xxx = reference value)
Zone reference value recording
xxx IP:yyy Port:zzz Online
xxx IP:yyy Port:zzz Offline
(xxx = remote name, yyy = ip address, zzz = port
number)
Ethernet remote connection status
xxx mic Offline
xxx mic Online
xxx Mic Disconnect
xxx Mic OK
xxx Mic Short
(xxx = remote name)
Ethernet remote mic status
Net Blacklist Machine (x,x)
There is some IDA8 communication is unstable