AH500 Hardware and Operation Manual
2-110
2.11.2 44BProfiles
AHRTU-DNET-5A
1. Profile
x10
1
x10
0
Node Address
DR 1
DR 0
IN 1
IN 0
1
2
3
4
7
6
8
9
11
10
5
Number
Name
Description
1
Model name
Model name of the module
2
Seven-segment display
Display
3
Address knobs
Setting the address
4
Function switch
Setting the functions
5 DeviceNet connector
DeviceNet is used to interconnect control devices for data
exchange.
6
MS LED indicator
Indicating the status of the module
7
NS LED indicator
Indicating the status of the network
8
Label
Nameplate
9
Set screw
Fixing the module
10
Connector
Connecting the module and a backplane
11
Projection
Fixing the module
2. Address knob
s
It is used to set the node address of AHRTU-DNET-5A on a DeviceNet network. (Node addresses
range from 0 to 63.)
Setting Description
0…63 Available nodes on a DeviceNet network
64…99 Unavailable nodes on a DeviceNet network
Example: If users want to set the communication address of AHRTU-DNET-5A to 26, they can turn
the knob corresponding to x10
1
to 2, and turn the knob corresponding to x10
0
to 6.
Points for attention:
When the power supply is cut off, the node address is set. After the setting of the node address
is complete, AHRTU-DNET-5A can be supplied with power.
If AHRTU-DNET-5A is running, changing the node address is unavailable.
Please use a slotted screwdriver to turn the knobs with care, and do not scrape them.