AH500 Hardware and Operation Manual 
2-110 
2.11.2  44BProfiles 
  AHRTU-DNET-5A 
1.  Profile 
x10
1
x10
0
Node Address
DR 1
DR 0
IN 1
IN 0
1
2
3
4
7
6
8
9
11
10
5
 
 
5  DeviceNet connector 
DeviceNet is used to interconnect control devices for data 
Indicating the status of the module 
Indicating the status of the network 
Connecting the module and a backplane 
 
2.  Address knob
s 
It is used to set the node address of AHRTU-DNET-5A on a DeviceNet network. (Node addresses 
range from 0 to 63.) 
Setting  Description 
0…63  Available nodes on a DeviceNet network 
64…99  Unavailable nodes on a DeviceNet network 
Example: If users want to set the communication address of AHRTU-DNET-5A to 26, they can turn 
the knob corresponding to x10
1
 to 2, and turn the knob corresponding to x10
0
 to 6. 
Points for attention: 
  When the power supply is cut off, the node address is set. After the setting of the node address 
is complete, AHRTU-DNET-5A can be supplied with power. 
  If AHRTU-DNET-5A is running, changing the node address is unavailable. 
  Please use a slotted screwdriver to turn the knobs with care, and do not scrape them.