AHPS05-5A
Item
Specifications
Supply voltage
100~240 VAC (-15%~10%)
50/60 Hz±5%
Maximum input
power
100 VAC/1.2A~240 VAC/0.68A; 70 W
Action
specifications
If the input power supply is larger than 85 VAC, the power supply module can
function normally.
Allowable
instantaneous
power failure time
If the instantaneous power failure time is within ten milliseconds, the power
supply module keeps running.
Fuse
4 A/250 VAC
Inrush current
45 A within 1 millisecond at 115 VAC
24 VDC output
The maximum current is 2.5 A.
It is only for a backplane.
Power protection
The 24 VDC output is equipped with the short circuit protection and the
overcurrent protection.
Maximum output
power
60 W
Surge voltage
withstand level
1,500 VAC (Primary-secondary), 1,500 VAC (Primary-PE), 500 VAC (Secondary-
PE)
Insulation voltage
Above 5 MΩ
(The voltage between all inputs/outputs and the ground is 500 VDC.)
Ground
The diameter of the ground should not be less than the diameters of the cables
connected to the terminals L and N.
Weight
380g
AHPS15-5A
Item
Specifications
Supply voltage
24 VDC (-35%, +30%)
Maximum input
power
24 VDC / 2A; 48 W
Allowable
instantaneous
power failure time
10 milliseconds
Fuse
6.3 A/250 VAC
Inrush current
30 A within 100 milliseconds
24 VDC output
1.5 A
Maximum output
power
36 W
Power protection
The 24 VDC output is equipped with the short circuit protection, the overcurrent
protection, and the overvoltage protection.
Surge voltage
withstand level
500 VAC
Ground
The diameter of the ground should be greater than 1.6 mm
2
.
Weight
380g