AH500 Hardware and Operation Manual 
12-8 
12.2.2
 
ERROR LED Indicator’s Blinking 
Error 
Description  Remedy 
16#000A 
Scan timeout 
(SM8: The watchdog timer error) 
1. Check the setting of the watchdog timer in 
HWCONFIG. 
2. Check whether the program causes the long scan time 
16#000C 
The program downloaded to the 
After users compile the program again, they can 
download the program again.   
16#000E 
The program or the parameter is 
being downloaded, and therefore 
After the program or the parameter is downloaded to the 
PLC, users can try to run the PLC. 
16#0018 
The serial port is abnormal. 
Retry the connection. If the error still occurs, please 
contact the local authorized distributors. 
16#0019  The USB is abnormal. (SM9) 
Retry the connection. If the error still occurs, please 
contact the local authorized distributors. 
16#001A 
Incorrect system backup file 
Generate a new system backup file fore restoration.   
16#0033 
The communication setting of 
COM1 is incorrect. (SM9) 
1. Check the program and the related special data 
registers. 
2. Set the communication port parameter for the CPU 
module in HWCONFIG again. 
16#0034 
The setting of the station address 
of COM1 is incorrect. (SM9) 
1. Check the program and the related special data 
registers. 
2. Set the communication port parameter for the CPU 
module in HWCONFIG again. 
16#0035 
The setting of the communication 
type of COM1 is incorrect. (SM9) 
1. Check the program and the related special data 
registers. 
2. Set the communication port parameter for the CPU 
module in HWCONFIG again. 
16#0038 
The communication setting of 
COM2 is incorrect. (SM9) 
1. Check the program and the related special data 
registers. 
2. Set the communication port parameter for the CPU 
module in HWCONFIG again. 
16#0039 
The setting of the station address 
of COM2 is incorrect. (SM9) 
1. Check the program and the related special data 
registers. 
2. Set the communication port parameter for the CPU 
module in HWCONFIG again. 
16#003A 
The setting of the communication 
type of COM2 is incorrect. (SM9) 
1. Check the program and the related special data 
registers. 
2. Set the communication port parameter for the CPU 
module in HWCONFIG again. 
16#0066 
An error occurs when the system 
is backed up. 
1. Check whether the memory card is normal, and 
whether the capacity of the memory card is large 
enough. 
2. Retry the backup procedure. If the error still occurs, 
please contact the local authorized distributors. 
16#0067 
The length of the restored system 
parameters exceeds the length of 
the CPU module system 
This error code is a warning code. 
Download the symbol table again. 
16#0069  Corrutped EIP parameters   
After users reset the CPU module or restore it to the 
factory setting, they can download the program and the