Chapter 4 Installing Hardware and Wiring
4-69
4.9.2 Wiring AH08AD-5B
V0+
V0-
*2
CH0
1M
AG
1M
SLD
V7+
V7-
*2
CH7
1M
AG
1M
SLD
CH0
CH7
*3
-10V~+10V
+
-
-10V~+10V
+
-
Shielded cable*1
Voltage input
Voltage input
Shielded cable*1
*1. Please use shielded cables to isolate the analog input signal cable from other power cables.
*2. If the ripple in the input voltage results in the noise interference with the wiring, please connect the module
to the capacitor having a capacitance in the range of 0.1 μF to 0.47 μF with a working voltage of 25 V.
*3. Please connect the terminal SLD to the ground terminal
.
4.9.3 Wiring AH08AD-5C
I0+
CH0
1M
AG
1M
SLD
I7+
I7-
CH 7
1M
AG
1M
SLD
CH0
CH 7
*2
I0-
250
250
-20mA~+20mA
+
-
+24V
0V
+
-
+24V
0V
I1+
I1-
CH1
1M
AG
1M
SLD
CH1
250
+24V
+
-
-20mA~+20mA
-20mA~+20mA
0V
Shielded cable 1*
Shielded cable 1*
Shielded cable 1*
4-wire: Current inp ut
3-wire: Current input
2-wire: Current inp ut
*1. Please use shielded cables to isolate the analog input signal cable from other power cables.
*2. Please connect the terminal SLD to the ground terminal .