Chapter 4 Installing Hardware and Wiring
4-77
4.11 Wiring Network Modules
4.11.1 Wiring AH10DNET-5A
4.11.1.1 DeviceNet Connector
Pin
Signal
Color
Description
1
2
3
4
5
5
V+
Red
24 VDC
4
CAN_H
White
Signal (positive pole)
3 SHIELD -
It is connected to a
shielded cable.
2
CAN_L
Blue
Signal (negative pole)
1 V- Black 0 VDC
4.11.1.2 Connecting a Cable to the DeviceNet Connector
Remove the 30 millimeter plastic jacket of a
cable with a professional tool. Please do not
damage the shielded cable when the plastic
jacket is removed.
After users remove the metallic shield and
the foil, they can see two power cables (in
red and black respectively), two signal
cables (in blue and white respectively), and
one shielded cable.
After the metallic shield and the foil are
removed, the users need to remove the
plastic jackets of the power cables and the
plastic jackets of the signal cables properly.
Insert the communication cable into the
holes in the connector.
After the communication cable is inserted
into the holes in the connector, tighten the
screws on the connector with a slotted
screwdriver.
Approximately 30 mm
Shielded cable
Blue (CAN_L)
Shielded cable (CAN_SHLD)
Black (V-)
Red (V+)
W
hite(CAN_H)