AH500 Hardware and Operation Manual
12-48
12.3.2
Troubleshooting for AH02HC-5A/AH04HC-5A
Error
code
Description Remedy
16#A001
The linear accumulation in
channel 0 exceeds the range.
To clear the linear accumulation, users need to set bit 1 in
CR0 to ON by means of FROM/TO.
16#A002
The scale set for channel 0
exceeds the range.
Check the module parameter in HWCONFIG.
The scale set for channel 0 should be in the range of 0 to
32767.
16#A003
The number of cycles set for
channel 0 exceeds the range.
Check the module parameter in HWCONFIG.
The number of cycles set for channel 0 should be in the
range of 2 to 60.
16#A004
The comparison value set for
channel 0 exceeds the range.
Check the module parameter in HWCONFIG.
The comparison value set for channel 0 should be in the
range of -999999999 to 999999999.
16#A005
A limit value set for channel 0 is
incorrect.
Check the module parameter in HWCONFIG.
A limit value of set for channel 0 should be in the range of
-200000 to 200000.
16#A006
The interrupt number set for
channel 0 exceeds the range.
Check the module parameter in HWCONFIG.
The interrupt number set for channel 0 should be in the
range of 0 to 31.
16#A011
The linear accumulation in
channel 1 exceeds the range.
To clear the linear accumulation, users need to set bit 1 in
CR28 to ON by means of FROM/TO.
16#A012
The scale set for channel 1
exceeds the range.
Check the module parameter in HWCONFIG.
The scale set for channel 1 should be in the range of 0 to
32767.
16#A013
The number of cycles set for
channel 1 exceeds the range.
Check the module parameter in HWCONFIG.
The number of cycles set for channel 1 should be in the
range of 2 to 60.
16#A014
The comparison value set for
channel 1 exceeds the range.
Check the module parameter in HWCONFIG.
The comparison value set for channel 1 should be in the
range of -999999999 to 999999999.
16#A015
A limit value set for channel 1 is
incorrect.
Check the module parameter in HWCONFIG.
A limit value of set for channel 1 should be in the range of
-200000 to 200000.
16#A016
The interrupt number set for
channel 1 exceeds the range.
Check the module parameter in HWCONFIG.
The interrupt number set for channel 1 should be in the
range of 0 to 31.
16#A021
The linear accumulation in
channel 2 exceeds the range.
To clear the linear accumulation, users need to set bit 1 in
CR56 to ON by means of FROM/TO.
16#A022
The scale set for channel 2
exceeds the range.
Check the module parameter in HWCONFIG.
The scale set for channel 2 should be in the range of 0 to
32767.
16#A023
The number of cycles set for
channel 2 exceeds the range.
Check the module parameter in HWCONFIG.
The number of cycles set for channel 2 should be in the
range of 2 to 60.
16#A024
The comparison value set for
channel 2 exceeds the range.
Check the module parameter in HWCONFIG.
The comparison value set for channel 2 should be in the
range of -999999999 to 999999999.
16#A025
A limit value set for channel 2 is
incorrect.
Check the module parameter in HWCONFIG.
A limit value of set for channel 2 should be in the range of
-200000 to 200000.
16#A026
The interrupt number set for
channel 2 exceeds the range.
Check the module parameter in HWCONFIG.
The interrupt number set for channel 2 should be in the
range of 0 to 31.