Chapter  4  Installing Hardware and Wiring 
4-83 
 
4.12.2 Wiring AHRTU-PFBS-5A 
4.12.2.1 Connecting the PROFIBUS-DP Connector 
  Insert the PROFIBUS-DP connector into the communication port on AHRTU-PFBS-5A. Tighten the 
screws on the PROFIBUS-DP connector to ensure that AHRTU-PFBS-5A is reliably connected to the 
PROFIBUS-DP connector. 
 
 
4.12.2.2 Definitions of the Pins in the PROFIBUS-
DP Port 
 
Receiving/Sending data (P (B)) 
Data reference potential (C) 
Supplying positive voltage (5 V) 
Receiving/Sending data (N (A)) 
4.12.2.3 Setting a PROFIBUS Node Address by the Knobs 
The address knobs on AHRTU-PFBS-5A are used to set the node address of AHRTU-PFBS-5A on a 
PROFIBUS-DP network. They are knobs which can be turned. One knob corresponds to x16
0
, and the other 
node corresponds to x16
1
. Setting range: 0~F 
Address  Definition 
H’1~H’7D  Valid PROFIBUS node address 
H’0 or H’7E~H’FF  Invalid PROFIBUS node address