AH500 Hardware and Operation Manual
4-102
2. An NPN encoder is used.
AH04HC-5A hig h-speed cou nte r module
A phase
B phase
PNP encoder
Shielde d cable
Externa l power supply
5~24VDC
5V, 12V, 24VDC
X0.8+
X0.8-
X0.9+
X0.9-
disable
Start
COM
+24V
OA
OB
OUT
OUT
0V
0V
+24V
Y0.8
C0
C1
X0.0+
X0.0-
Y0.9
Shielde d cable
Shielde d cable
External power supply
4.13.3.2 Wiring the Differential Input Terminals
The direct-current signals ranging in voltage from 5 V to 24 V can pass through the high-speed input terminals
X0.0+~X0.1+, X0.0-~X0.1-, X0.8+~X0.11+, and X0.8-~X0.11- on AH02HC-5A, and the high-speed input
terminals X0.0+~X0.3+, X0.0-~X0.3-, X0.8+~X0.15+, and X0.8-~X0.15- on AH04HC-5A. The frequency of
input signals can be up to 200 kHz. These high-speed input terminals are connected to a differential (two-wire)
line driver.
Wiring differential input terminals (The wiring below is used for high speed and high noise.)
AH04HC-5A high-speed input
A-
X0.8 +
X0.8 -
A+
A
B-
X0.9+
X0.9-
B +
B
Encoder output