Chapter 12 Troubleshooting
12-63
12.4.1
CPU Modules
Error
code
Description
CPU
Status
ERROR
BUS
16#000A
Scan timeout
(SM8: The watchdog timer error)
Stop Blinking Keep
The program in the PLC is damaged.
The program downloaded to the PLC is incorrect.
The CPU parameter is damaged.
16#000E
The program or the parameter is being downloaded,
and therefore the PLC can not run.
Stop Blinking Keep
The original program in the PLC is damaged.
The access to the memory in the CPU is denied.
The PLC ID is incorrect. (SM9)
The PLC password is incorrect.
The I/O module can not run/stop. (SM10)
16#0014
The procedure of restoring the system can not be
Stop ON ON
The module table is incorrect. (SM10)
The module setting is incorrect. (SM10)
16#0017
The device which is associated with the data register is
Stop ON Keep
The serial port is abnormal. (SM9)
The USB is abnormal. (SM9)
16#001A
The contents of the system backup file (DUP) are
Stop ON Keep
Timed interrupt 0 is set incorrectly.
Timed interrupt 1 is set incorrectly.
Timed interrupt 2 is set incorrectly.
Timed interrupt 3 is set incorrectly.
The watchdog timer is set incorrectly.
The setting of the fixed scan time is incorrect.
The setting of the fixed scan time is incorrect.
16#0022
The CPU parameter downloaded to the PLC is
Stop ON Keep
16#0023
The Y state (STOP->RUN) section in the PLC
Parameter Setting window is set incorrectly.
Stop ON Keep
There is no I/O module on a backplane.
16#0025
The initial value of the symbol is not consistant with
what is set in the program.
Stop ON Keep
16#0026
The latching auxiliary relay range which is set is
Stop ON Keep
16#0027
The latching data register range which is set is
Stop ON Keep
The latching timer range which is set is incorrect.
The latching counter range which is set is incorrect.
16#002A
The latching 32-bit counter range which is set is
Stop ON Keep
16#002B
The latching auxiliary relay range which is set is
Stop ON Keep
16#0033
The communication setting of COM1 is incorrect.
Continue Blinking Keep
16#0034
The setting of the station address of COM1 is incorrect.
Continue Blinking Keep