EasyManua.ls Logo

Delta AH500 - 2.2.2 AH500 Series Advanced CPU Modules

Delta AH500
681 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AH500 Hardware and Operation Manual
2-6
2.2.2 13BAH500 Series Advanced CPU Modules
Item
AHCPU501/511/521/
531-RS2
AHCPU501/511/521/
531-EN and AHCPU521-
DNP
Remark
Execution
The program is executed cyclically.
Input/Output control
Regenerated inputs/outputs
Direct inputs/outputs
The inputs and
outputs can be
controlled through the
direct inputs and
direct outputs.
Programming language
IEC 61131-3
Ladder diagrams, function block diagrams,
instruction lists, structured texts, and sequential
function charts
Instruction execution speed
12K steps/ms
Number of instructions
Approximately 666 instructions
Constant scan cycle (ms)
1-32000
(The scan cycle can be increased by one
millisecond.)
Setting the parameter
Program capacity (step)
AHCPU501: 48 steps
AHCPU511: 96K steps
AHCPU521: 192K steps
AHCPU531: 384K steps
Installation
DIN rails or screws
Installation of a module
A module is installed directly on a backplane.
Connection between two
backplanes
An extension cable connects two backplanes.
Maximum number of
modules which can be
installed
AHCPU501: 12 modules
AHCPU511: 20 modules
AHCPU521: 36 modules
AHCPU531: 68 modules
Maximum number of
backplanes which can be
connected
AHCPU501: 1 main backplane
AHCPU511: 2 backplane (1 main backplane+1
extension backplane)
AHCPU521: 4 backplanes (1 main backplane+3
extension backplane)
AHCPU531: 8 backplanes (1 main backplane+7
extension backplanes)
Number of tasks
283 tasks (32 cyclic tasks; 32 I/O interrupts; 4
timed interrupts; 2 communication interrupts; 1
external 24 V low-voltage interrupt; 212 external
interrupts)
Number of inputs/outputs
AHCPU501: 768
AHCPU511: 1280
AHCPU521: 2304
AHCPU531: 4352
Number of
inputs/outputs
accessible to an
actual input/output
module
Input relays [X]
AHCPU501: 2048 (X0.0~X127.15)
AHCPU511: 4096 (X0.0~X255.15)
AHCPU521: 8192 (X0.0~X511.15)
AHCPU531: 16384 (X0.0~X1023.15)
Output relays [Y]
AHCPU501: 2048 (Y0.0~X127.15)
AHCPU511: 4096 (Y0.0~Y255.15)
AHCPU521: 8192 (Y0.0~Y511.15)
AHCPU531: 16384 (Y0.0~Y1023.15)
Internal relays [M]
8192 (M0~M8191)