Chapter 12 Troubleshooting
12-5
12.2
Troubleshooting for CPU Modules
Users can get the remedies from the tables below according to the statuses of the LED indicators and the error
codes.
12.2.1
ERROR LED Indicator’s Being ON
Error
code
Description Remedy
16#000B
The program in the PLC is
damaged.
Download the program again.
16#000D
The CPU parameters are
damaged.
Reset the CPU parameter, and download it.
16#0010
The access to the memory in the
CPU is denied.
Download the program or parameters again. If the
problem still occurs, please contact the local authorized
distributors.
16#0011
The PLC ID is incorrect. (SM9)
Please check the PLC ID.
16#0012
The PLC password is incorrect.
(SM9)
Please check the PLC password.
16#0014
The procedure of restoring the
system can not be executed.
(SM9)
The contents of the system backup file are incorrect, or
the file does not exist in the path specified. If the file
exists and the procedure of restoring the system can not
be executed, please backing up the system again. If the
error still occurs, please contact the local authorized
distributors. (Please refer to section 7.5 in AH500
Operation Manual, and section 21 in ISPSoft User
Manual for more information about the memory card.)
16#0015
The module table is incorrect.
(SM10)
The module table stored in the CPU module is incorrect.
Compare the module table in HWCONFIG with the actual
module configuration, and download the module table
again.
16#0016
The module setting is incorrect.
(SM10)
The module setting stored in the CPU module is
incorrect. Check whether the version of the module
inserted in the slot is the same as the version of the
module in HWCONFIG. After the version of the module is
updated, users can download the module setting again.
16#0017
The data register exceeds the
device range. (SM10)
The data register stored in the CPU module exceeds the
device range. Check whether the module parameter in
HWCONFIG is correct, and download the module
parameter again.
16#001B Timed interrupt 0 is set incorrectly.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#001C Timed interrupt 1 is set incorrectly.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#001D Timed interrupt 2 is set incorrectly.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#001E Timed interrupt 3 is set incorrectly.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#001F
The watchdog timer is set
incorrectly.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#0020
The setting of the fixed scan time
is incorrect.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#0021
The setting of the fixed scan time
is incorrect.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#0022
The CPU parameter downloaded
to the PLC is incorrect.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.