11.1.3  Executing a PLC Link through the Program in ISPSoft 
Users can execute a PLC Link through the program in ISPSoft. The setting of the parameters related to a PLC 
Links is described in this section. Users can execute a PLC Link efficiently. 
11.1.3.1  Parameters Related to a PLC Link 
1.  The special data registers and the special auxiliary relays for slave 1~slave 32 are described below. 
Latched area 
Address in 
the master: 
The device 
address into 
which the 
data is read 
(SR1404 and 
Address in 
the master: 
The device 
address from 
which the 
data is written 
(SR1468 and 
Address in 
the master: 
The device 
address into 
which the 
data is read 
(SR1406 and 
Address in 
the master: 
The device 
address from 
which the 
data is written 
(SR1470 and 
… 
Address in 
the master: 
The device 
address into 
which the 
data is read 
(SR1466 and 
Address in 
the master: 
The device 
address from 
which the 
data is written 
(SR1530 and 
Address in 
the slave: 
The device 
address from 
which the 
data is read 
(SR1532 and 
Address in 
the slave: 
The device 
address into 
which the 
data is written 
(SR1596 and 
Address in 
the slave: 
The device 
address from 
which the 
data is read 
(SR1534 and 
Address in 
the slave: 
The device 
address into 
which the 
data is written 
(SR1598 and 
… 
Address in 
the slave: 
The device 
address from 
which the 
data is read 
(SR1594 and 
Address in 
the slave: 
The device 
address into 
which the 
data is written 
(SR1658 and 
Number of 
data which is 
read from the 
slave 
Number of 
data which is 
written into 
the slave 
Number of 
data which is 
read from the 
slave 
Number of 
data which is 
written into 
the slave 
… 
Number of 
data which is 
read from the 
slave 
Number of 
data which is 
written into 
the slave 
… 
Type of slave 32 (SR1755) 
Address of slave 1 (SR1756) 
Address of slave 2 (SR1757) 
Address of slave 32 (SR1787) 
Non-latched area 
Data exchange flag (SM1424) 
Data exchange flag (SM1425) 
Data exchange flag (SM1455) 
Read error 
flag 
Write error 
flag 
Read error 
flag 
Write error 
flag 
… 
Read error 
flag 
Write error 
flag 
The data reading is complete. 
(ON->OFF) (SM1520) 
The data reading is complete. 
(ON->OFF) (SM1521) 
… 
The data reading is complete. 
(ON->OFF) (SM1551) 
The data writing in the PLC 
Link is complete. (ON->OFF) 
The data writing in the PLC 
Link is complete. (ON->OFF) 
… 
The data writing in the PLC 
Link is complete. (ON->OFF) 
*. SM1424~SM1583 are read-only devices.   
 
  Start address in the master station: The start address in the master station is a device address. The 
default start address in the master station is D0. If the AH500 Modbus communication protocol is used, 
the start address in the master station is an AH500 Modbus device address. If the standard Modbus 
communication protocol is used, the start address in the master station is a Modbus device address. 
The data in the device addresses in the master station starting from the start address in the master 
station is sent to a slave, and the data sent by a slave station is stored in the devices in the master 
station starting from the start address in the master station. If the communication protocol used is the 
standard Modbus communication protocol, only M0~M8191 and D0~D32767 can be used. If the 
communication protocol used is the AH500 Modbus communication protocol, only M0~M8191,