AH500 Hardware and Operation Manual
9-40
9.3.3 Using Routing in ISPSoft
After users create a network architecture in NWCONFIG, and download the routing tables produced to PLCs,
they can download data to a device which is not directly connected to ISPSoft through routing, upload data
from a device which is not directly connected to ISPSoft through routing, or monitor data in a device which is
not directly connected to ISPSoft through routing. If the users want to use routing in ISPSoft, the devices used
must be AH500 series CPU modules.
In the figure below, the PLC which actually connects to the computer is AH-01. AH-03 can be monitored
through routing.
(1) Users have to activate the project for AH-03.
(2) Click the Tools menu, and then click Communication Settings.
(3) In the Communication Setting window, the users have to select the Routing Mode checkbox, and