AH500 Hardware and Operation Manual
C-2
C.1 EMC Standards for an AH500 System
C.1.1 EMC Standards Applicable to an AH500 System
The EMC standards which are applicable to an AH500 system are listed below.
EMI
Port
Frequency range
Level (Normative)
Reference standard
Enclosure port
(radiated)
(measured at a
distance of 10 meters)
30-230 MHz 40 dB (μV/m) quasi-peak
IEC 61000-6-4
230-1000 MHz 47 dB (μV/m) quasi-peak
AC power port
(conducted)
0.15-0.5 MHz
79 dB (μV) quasi-peak
IEC 61000-6-4
66 dB (μV) average
0.5-30 MHz
73 dB (μV) quasi-peak
60 dB (μV) average
EMS
Environmental
phenomenon
Reference
standard
Test Test level
Electrostatic
discharge
IEC 61000-4-2
Contact
± 4 kV
Air
± 8 kV
Radio frequency
electromagnetic field
Amplitude modulated
IEC 61000-4-3
80% AM,
1 kHz sinusoidal
2.0-2.7 GHz
1 V/m
1.4-2.0 GHz
3 V/m
80-1000 MHz
10 V/m
Power frequency
magnetic field
IEC 61000-4-8
60 Hz
30 A/m
50 Hz
30 A/m
Conducted immunity test
Environmental phenomenon
Fast transient
burst
High energy surge
Radio frequency
interference
Reference standard
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
Interface/Port
Specific
interface/port
Test level Test level Test level
Data
communication
Shielded cable
1 kV
1 kV CM
10V
Unshielded cable
1 kV
1 kV CM
10V
Digital and analog
I/O
AC I/O
(unshielded)
2 kV
2 kV CM
1 kV DM
10V
Analog or DC
I/O(unshielded)
1 kV 1 kV CM 10V
All shielded lines
(to the earth)
1 kV 1 kV CM 10V
Equipment power
AC power 2 kV
2 kV CM
1 kV DM
10V
DC power 2 kV
0.5 kV CM
0.5 kV DM
10V
I/O power and
auxiliary power
output
AC I/O and AC
auxiliary power
2 kV
2 kV CM
1 kV DM
10V
DC I/O and DC
auxiliary power
2 kV
0.5 kV CM
0.5 kV DM
10V

Table of Contents