Chapter 11  Convenient Functions 
11-31 
11.1.4  Related Special Auxiliary Relays and Special Data Registers 
1.  Descriptions of the related special auxiliary relays: 
SM1584 
Enabling the function of executing a 
PLC Link 
R/W 
OFF: The function of executing a PLC Link 
is disabled. (Default) 
ON: The function of executing a PLC Link 
SM1585 
Connecting to the slave stations 
automatically/manually 
R/W 
Using user-defined PLC Link flags 
*1
 
OFF: The user-defined PLC Link flags are 
not used. 
ON: The user-define PLC Link flags are 
SM1586 
Executing a PLC Link in the 
automatic mode 
R/W 
PLC Link in the automatic   
OFF: Not executing a PLC Link in the 
automatic mode (Default) 
ON: Executing a PLC Link in the automatic 
SM1587 
Executing a PLC Link in the manual 
mode 
R/W 
PLC Link in the manual mode 
OFF: Not executing a PLC Link in the 
manual mode (Default) 
ON: Executing a PLC Link in the manual 
SM1588 
Enabling the function of detecting 
the slave stations automatically 
R 
Detecting the slave stations 
OFF: The master does not detect the 
slaves. 
ON: The master station detects the slave 
SM1589  PLC Link error flag  R 
If SM1586 and SM1587 are ON, SM1589 
will be ON. 
OFF: No error occurs. 
SM1590  A device address is incorrect.  R 
If a device address is incorrect, SM1590 will 
be ON. 
OFF: A device address is incorrect. 
ON: No device address is incorrect. 
SM1591  Timeout  R 
I
f there is a communication timeout, SM1591 
will be ON. 
OFF: There is no communication timeout.   
ON: There is a communication timeout. 
SM1592 
The number of polling cycles in a 
PLC link is incorrect. 
R 
If the value in SR1338 is 0, SM1592 will be 
ON. 
OFF
: The number of times the master station 
polls the slave station is correct. 
ON: The number of times the master station 
polls the slave stations is incorrect. 
SM1593 
Standard Modbus communication 
protocol/AH500 Modbus 
communication protocol 
R/W 
Selecting a communication protocol 
OFF: Standard Modbus communication 
protocol (Default) 
ON: AH500 Modbus communication protocol 
SM1594 
Detecting the slave stations 
automatically 
R/W 
The master station will detect the slave 
stations automatically o
the PLC Link stops. 
OFF: The master station finishes detecting 
the slave stations, or waits to detect 
the slave stations. (Default)