AH500 Hardware and Operation Manual 
12-14 
12.2.3
 
BUS FAULT LED Indicator’s Being ON
 
When a CPU module detects an error, the BUS FAULT LED indicator on the CPU module is ON. The BUS 
FAULT LED indicator on the CPU module corresponds to the ERROR LED indicator on an I/O module. If an 
error occurs in an I/O module, the status of the BUS FAULT LED indicator on the CPU module is the same as 
that of the ERROR LED indicator on the I/O module. If there are errors occurring in the I/O modules, the BUS 
FAULT LED indicator on the CPU module will be ON. For example, the BUS FAULT LED indicator on the CPU 
module will be ON if the ERROR LED indicator on I/O module A is ON and the ERROR LED indicator on I/O 
module B blinks. If the ERROR LED indicator on I/O module B still blinks after the error occurring in I/O module 
A is eliminated, the BUS FAULT LED indicator on the CPU module will blink. Please refer to sections 12.4 in 
this manual for more information about the LED indicators. 
Users can get the remedies for the errors detected by a CPU module from the table below. If the error code 
which users get is not listed in the table below, users need to check whether the I/O module operates normally. 
Please refer to section 12.3 in this manual for more information about the troubleshooting for I/O modules. 
 
Error 
Description  Remedy 
16#0013 
The I/O module can not run/stop. 
(SM10) 
Check whether the setting of the parameter for the 
module is correct. If the setting is correct, please check 
whether the module breaks down. If the error still occurs, 
please contact the local authorized distributors. 
16#0014 
The procedure of restoring the 
system can not be executed. 
(SM9) 
The contents of the system backup file are incorrect, or 
the file does not exist in the path specified. If the file 
exists and the procedure of restoring the system can not 
be executed, please backing up the system again. If the 
error still occurs, please contact the local authorized 
distributors. (Please refer to section 7.5 in AH500 
Operation Manual, and section 18.2 in ISPSoft User 
Manual for more information about the memory card.) 
16#1400 
An error occurs when the data 
is accessed through the 
auxiliary processor. (SM9) 
Check and eliminate the problem. If the problem persists, 
contact the local authorized 
16#1401 
An error occurs when the data in 
the I/O module is accessed. 
Check and eliminate the problem. If the problem persists, 
contact the local authorized 
16#1402 
The actual arrangement of the I/O 
modules is not consistent with the 
Check whether the module table in HWCONFIG is 
consistent with the actual arrangement of the I/O 
16#1403 
An error occurs when the data is 
read from the module. (SM9) 
Check whether the module operates normally. If the error 
still occurs, please contact the local authorized 
16#1405 
The setting parameter of the 
module is not found. (SM9) 
Set the parameter in HWCONFIG again, and download it. 
16#1407 
A communication error occurs 
when the data is accessed 
through the auxiliary processor. 
Check and eliminate the problem. If the problem persists, 
contact the local authorized distributors. 
16#1409 
The extension backplane is 
disconnected. (SM9) 
1. Check whether the extension backplane is connected 
properly and make sure the settings on the HWCOFIG 
is the same as the actual placement.   
2. Check whether the extension backplane operates 
normally, and make sure that the extension backplane 
is not affected by noise.