AH500 Hardware and Operation Manual 
12-92 
12.4.11
 
AH10COPM-5A 
Error code  Description 
16#A0B0 
AH10COPM-5A does not send a heartbeat message after 
a set period of time. 
Blinking 
The red light 
flashes twice. 
16#A0B1 
The length of a PDO that a slave station sends is not the 
same as the length of the PDO set in the node list. 
Blinking  OFF 
16#A0B2 
The master station selected does not send a node 
guarding message after a set period of time. 
Blinking 
The red light 
flashes twice. 
16#A0E0 
AH10COPM-5A receives an emergency message from a 
Blinking  OFF 
16#A0E1 
The length of a PDO that a slave station sends is not the 
same as the length of the PDO set in the node list. 
Blinking  OFF 
16#A0E2 
AH10COPM-5A does not receive a PDO from a slave 
Blinking  OFF 
16#A0E3  An automatic SDO is not downloaded successfully.  Blinking  OFF 
16#A0E4  A PDO parameter is not set successfully.  Blinking  OFF 
16#A0E5  A key parameter is set incorrectly.  Blinking  OFF 
16#A0E6 
The actual network configuration is not the same as the 
network configuration set. 
Blinking  OFF 
16#A0E7 
The control of the errors in a slave station is not sent after 
a set period of time. 
Blinking 
The red light 
flashes twice. 
16#A0E8 
The master station address is the same as a slave station 
Blinking  OFF 
16#A0F1 
No slave station is added to the node list in CANopen 
builder. 
Blinking  OFF 
16#A0F3  An error occurs in AH10COPM-5A.  Blinking  OFF 
16#A0F4  The bus used is off.  Blinking 
16#A0F5  The node address of AH10COPM-5A is set incorrectly.  Blinking  OFF 
16#A0F6 
Internal error: An error occurs in the manufacturing 
process in the factory. 
Blinking  OFF 
16#A0F7  Internal error: GPIO error  Blinking  OFF 
16#A0F8  Hardware error  Blinking  OFF 
16#A0F9  Low voltage  Blinking  OFF 
16#A0FA  An error occurs in the firmware of AH10COPM-5A.  Blinking  OFF 
16#A0FB  The transmission registers in AH10COPM-5A are full.  Blinking  OFF 
16#A0FC  The reception registers in AH10COPM-5A are full.  Blinking  OFF