12-86
12.4.4
AH05PM-5A/AH10PM-5A/AH15PM-5A
Error code Description
LED indicator status
CPU
Module
BUS FAULT
ERROR
16#A002
The subroutine has no data.
Blinking
16#A003
CJ, CJN, and JMP have no matching pointers.
Blinking
16#A004
There is a subroutine pointer in the main program.
Blinking
16#A005
Lack of the subroutine
Blinking
16#A006
The pointer is used repeatedly in the same program.
Blinking
16#A007
The subroutine pointer is used repeatedly.
Blinking
16#A008
The pointer used in JMP is used repeatedly in different
subroutines.
Blinking
16#A009
The pointer used in JMP is the same as the pointer used in
CALL.
Blinking
16#A00A
The pointer used in JMP is the same as a subroutine pointer.
Blinking
16#A00B
Target position (I) of the single speed is incorrect.
Blinking
16#A00C
Target position (II) of the single-axis motion is incorrect.
Blinking
16#A00D
The setting of speed (I) of the single-axis motion is incorrect.
Blinking
16#A00E
The setting of speed (II) of the single-axis motion is incorrect.
Blinking
16#A00F
The setting of the speed (V
RT
) of returning to zero is incorrect.
Blinking
16#A010
The setting of the deceleration (V
CR
) of returning to zero is
incorrect.
Blinking
16#A011
The setting of the JOG speed is incorrect.
Blinking
16#A012
The positive pulses generated by the single-axis clockwise
motion are inhibited.
Blinking
16#A013
The negative pulses generated by the single-axis
counterclockwise motion are inhibited.
Blinking
16#A014
The limit switch is reached.
Blinking
16#A015
The device which is used exceeds the device range.
Blinking
16#A017
An error occurs when the device is modified by a 16-bit index
register/32-bit index register.
Blinking
16#A018
The conversion into the floating-point number is incorrect.
Blinking
16#A019
The conversion into the binary-coded decimal number is
incorrect.
Blinking
16#A01A
Incorrect division operation (The divisor is 0.)
Blinking
16#A01B
General program error
Blinking
16#A01C
LD/LDI has been used more than nine times.
Blinking
16#A01D
There is more than one level of nested program structure
supported by RPT/RPE.
Blinking
16#A01E
SRET is used between RPT and RPE.
Blinking
16#A01F
There is no M102 in the main program, or there is no M2 in the
motion program.
Blinking
16#A020
The wrong instruction is used, or the device used exceeds the
range.
Blinking

Table of Contents

Other manuals for Delta AH500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AH500 and is the answer not in the manual?

Delta AH500 Specifications

General IconGeneral
BrandDelta
ModelAH500
CategoryController
LanguageEnglish

Related product manuals