Chapter 12 Troubleshooting
12-89
12.4.8
AH10DNET-5A
Error code Description
LED indicator status
CPU
Module
BUS FAULT
MS
NS
16#A0F0
The node ID of AH10DNET-5A is the
same as other node ID on the network,
or exceeds the range.
The red light blinks.
The green
light blinks.
The red light
is ON.
16#A0F1
No slave is put in the scan list of
AH10DNET-5A.
The red light blinks.
The green
light blinks.
The green
light is ON.
16#A0F2
The working voltage of AH10DNET-5A
is low.
The red light blinks.
The red light
blinks.
The red light
blinks.
16#A0F3 AH10DNET-5A enters the test mode. The red light blinks.
The orange
light is ON.
The orange
light is ON.
16#A0F4
The bus of AH10DNET-5A is switched
OFF.
The red light blinks.
The green
light is ON.
The red light
is ON.
16#A0F5
AH10DNET-5A detects that there is no
network power supply to the DeviceNet.
The red light blinks.
The red light
blinks.
The red light
is ON.
16#A0F6
Something is wrong with the internal
memory of AH10DNET-5A.
The red light blinks.
The red light
is ON.
The green
light blinks.
16#A0F7
Something is wrong with the data
exchange unit of AH10DNET-5A.
The red light blinks.
The red light
is ON.
The green
light blinks.
16#A0F8
The product ID of AH10DNET-5A is
incorrect.
The red light blinks.
The red light
is ON.
The green
light blinks.
16#A0F9
An error occurs when the data is read
from AH10DNET-5A, or when the data
is written into AH10DNET-5A.
The red light blinks.
The red light
is ON.
The red light
is ON.
16#A0FA
The node ID of AH10DNET-5A is the
same as that of the slave set in the
scan list.
The red light blinks.
The green
light is ON.
The red light
is ON.
16#A0FB
The data exchange between
AH10DNET and AH CPU failed.
The red light blinks.
The green
light is ON.
The green
light is ON.
16#A0FC
Errors occur in the slaves, on the
module of an AHRTU-DNET
backplane, or on the AHRTU-DNET
backplane connection.
The red light blinks.
The red light
blinks.
The green
light is ON.