Chapter 12  Troubleshooting 
12-59 
12.3.9
 
Troubleshooting for AH10PFBS-5A 
Error 
Description  Remedy 
16#A4F0 
AH10PFBS-5A exceeds the 
The node address of AH10PFBS-5A must be in the range 
of 1 to 125. 
16#A4F1  Internal hardware error 
If the error still exists after repowering AH10PFBS-5A, 
replace it with a new one. 
16#A4F2  Parameter error 
Check whether the GSD file AH10PFBS-5A is using is 
correct. 
16#A4F3  Configuration error 
Check whether the GSD file AH10PFBS-5A is using is 
16#A4F4  GPIO detection error 
If the error still exists after repowering AH10PFBS-5A, 
replace it with a new one. 
16#A4F5 
AH10PFBS-5A enters the mode 
Repower AH10PFBS-5A after setting its node address 
16#A4F6 
been connected to the 
PROFIBUS-DP network. 
2.  PROFIBUS-DP master has 
not configured 
AH10PFBS-5A slave or the 
configured node address of 
AH10PFBS-5A is 
inconsistent with that of the 
1.  Check whether the communication cable between 
AH10PFBS-5A and PROFIBUS-DP master is in 
normal status. 
2.  Ensure that AH10PFBS-5A slave has been configured 
to PROFIBUS-DP master and the configured node 
address of AH10PFBS-5A is consistent with that of the 
actually connected one. 
3.  Check whether the PROFIBUS-DP master works 
normally.