Chapter 12 Troubleshooting
12-59
12.3.9
Troubleshooting for AH10PFBS-5A
Error
code
Description Remedy
16#A4F0
The node address of
AH10PFBS-5A exceeds the
valid range.
The node address of AH10PFBS-5A must be in the range
of 1 to 125.
16#A4F1 Internal hardware error
If the error still exists after repowering AH10PFBS-5A,
replace it with a new one.
16#A4F2 Parameter error
Check whether the GSD file AH10PFBS-5A is using is
correct.
16#A4F3 Configuration error
Check whether the GSD file AH10PFBS-5A is using is
correct.
16#A4F4 GPIO detection error
If the error still exists after repowering AH10PFBS-5A,
replace it with a new one.
16#A4F5
AH10PFBS-5A enters the mode
of factory test.
Repower AH10PFBS-5A after setting its node address
between 1~125.
16#A4F6
1. AH10PFBS-5A has not
been connected to the
PROFIBUS-DP network.
2. PROFIBUS-DP master has
not configured
AH10PFBS-5A slave or the
configured node address of
AH10PFBS-5A is
inconsistent with that of the
actually connected one.
1. Check whether the communication cable between
AH10PFBS-5A and PROFIBUS-DP master is in
normal status.
2. Ensure that AH10PFBS-5A slave has been configured
to PROFIBUS-DP master and the configured node
address of AH10PFBS-5A is consistent with that of the
actually connected one.
3. Check whether the PROFIBUS-DP master works
normally.