Chapter 2 Specifications and System Configuration
2-9
Item
AHCPU560-EN2 Remark
MODBUS TCP connection
number (Master)
128
USB port
Mini USB
Storage interface
Micro SD
Remote RUN/STOP
The setting range is X0.0~X511.15.
Real-time clock
Years, months, days, hours, minutes, seconds, and weeks;
real-time clock can be retained after power-off for up to 30
days (the environment temperature 25
o
C / 77
o
F)
Real-time clock accuracy
Maximum deviation per month
-20
o
C / -4
o
F: -117 seconds
25
o
C / 77
o
F: 52 seconds
60
o
C / 140
o
F: -127 seconds
Switchover Time
For modules on extension backplane: under 20 ms
For remote I/O modules (Master CPU controls): under 2 s
Synchronization speed
0.5 ms / kbyte
Weight
265g
Communication
port isolation
USB and COM ports: 500 VAC
Ethernet: 1500 VAC
2.2.4 14BProfiles
2.2.4.1 AH500 Basic/Advanced CPU modules
AHCPU5X0-RS2 (AHCPU500-RS2/AHCPU510-RS2/AHCPU520-RS2/AHCPU530-RS2),
AHCPU5X1-RS2 (AHCPU501-RS2/AHCPU511-RS2/AHCPU521-RS2/AHCPU531-RS2)
Built-in communication ports*2 (RS-232 and RS-422/485)
CPU530-RS2
RUN
ERROR
BUS FAULT
SYSTE M
COM1
COM2
C
O
M
C
O
M
2
1
USB
C
O
M
C
O
M
2
1
1
12
2
3
4
6
7
13
6
8
9
11
10
14
15