Chapter  2  Specifications  and System Configuration 
2-63 
  AH04TC-5A/AH08TC-5A 
Electrical specifications 
4  8 
Applicable sensor 
Type J, type K, type R, type S, type T, type E, and type N thermocouples 
24 VDC (20.4 VDC~28.8 VDC) (-15%~+20%) 
Overall accuracy 
25°C/77°F: The error is ±0.5% of the input within the range 
-20~60°C/-4~140°F: The error is 
±
1% of the input within the range 
Isolation 
An analog circuit is isolated from a digital circuit by a digital integrated circuit/an 
optocoupler, and the analog channels are isolated from one another by 
optocouplers. 
Isolation between a digital circuit and a ground: 500 VDC 
Isolation between an analog circuit and a ground: 500 VDC 
Isolation between an analog circuit and a digital circuit: 500 VDC 
Isolation between the 24 VDC and a ground: 500 VDC 
Isolation between analog channels: 120 VAC 
Weight  190g 
 
Functional specifications 
Analog-to-digital 
Centigrade (°C)  Fahrenheit (°F)  Voltage input 
Rated input range 
Type K: -100°C~1,350°C 
Type R: 0°C~1,750°C 
Type S: 0°C~1,750°C 
Type T: -150°C~390°C 
Type E: -150°C~980°C 
Type K: -148°F~2,462°F 
Type R: 32°F~3,182°F 
Type S: 32°F~3,182°F 
Type T: -238°F~734°F 
Type E: -238°F~1,796°F 
±150 mV 
 
2.8.2  Profiles 
  AH04PT-5A/AH04TC-5A/AH08TC-5A 
I1
O1
O0
I3
O3
I0
RUN
ERROR
O2
I2
I0
FG
I1
04PT
O0
FG
O1
I3
I2
FG
O2
FG
RTD
2/3/4-WIRE
O3
1
2
3
4
7
6
8
9
10
5
I3
FG
FG
I3
Thermocouple
J,K ,R, S,T, E, N
I2
I2
I1
I1
I0
I0
08TC
RUN
ERROR
I6
I5
I5
I4
I7
FG
I7
I6
FG
I4
I0
I0
04TC
I3
FG
FG
I3
RUN
ERROR
I2
I2
I1
I1
Thermocouple