AH500 Hardware and Operation Manual
12-6
Error
code
Description Remedy
16#0023
The PLC parameter: the state of Y
device (STOP->RUN) is set
incorrectly.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
16#0025
The initial value of the symbol is
not consistant with what is set in
the program.
Download the symbol table again.
16#0026
Communication Ratio is set
incorrectly.
After users reset the CPU module or restore it to the
factory setting, they can download the program and the
parameter again.
16#0027
M device in the Latched Device
Range is set incorrectly.
After users reset the CPU module or restore it to the
factory setting, they can download the program and the
parameter again.
16#0028
D device in the Latched Device
Range is set incorrectly.
After users reset the CPU module or restore it to the
factory setting, they can download the program and the
parameter again.
16#0029
T device in the Latched Device
Range is set incorrectly.
After users reset the CPU module or restore it to the
factory setting, they can download the program and the
parameter again.
16#002A
C device in the Latched Device
Range is set incorrectly.
After users reset the CPU module or restore it to the
factory setting, they can download the program and the
parameter again.
16#002B
HC device in the Latched Device
Range is set incorrectly.
After users reset the CPU module or restore it to the
factory setting, they can download the program and the
parameter again.
16#0050
The memories in the latched
special auxiliary relays are
abnormal.
After users reset the CPU module or restore it to the
factory setting, they can download the program and the
parameter again.
16#0051
The latched special data registers
are abnormal.
After users reset the CPU module or restore it to the
factory setting, they can download the program and the
parameter again.
16#0052
The memories in the latched
auxiliary relays are abnormal.
After users reset the CPU module or restore it to the
factory setting, they can download the program and the
parameter again.
16#0053 The latched timers are abnormal.
After users reset the CPU module or restore it to the
factory setting, they can download the program and the
parameter again.
16#0054
The latched counters are
abnormal.
After users reset the CPU module or restore it to the
factory setting, they can download the program and the
parameter again.
16#0055
The latched 32-bit counters are
abnormal.
After users reset the CPU module or restore it to the
factory setting, they can download the program and the
parameter again.
16#0056
The memories in the latched
timers are abnormal.
After users reset the CPU module or restore it to the
factory setting, they can download the program and the
parameter again.
16#0057
The memories in the latched
counters are abnormal.
After users reset the CPU module or restore it to the
factory setting, they can download the program and the
parameter again.
16#0058
The memories in the latched
32-bit counters are abnormal.
After users reset the CPU module or restore it to the
factory setting, they can download the program and the
parameter again.
16#0059
The latched data registers are
abnormal.
After users reset the CPU module or restore it to the
factory setting, they can download the program and the
parameter again.