AH500 Hardware and Operation Manual
12-64
Error
code
Description
CPU
Status
LED indicator status
ERROR
BUS
FAULT
16#0035
The setting of the communication type of COM1 is
incorrect. (SM9)
Continue Blinking Keep
16#0038
The communication setting of COM2 is incorrect.
(SM9)
Continue Blinking Keep
16#0039
The setting of the station address of COM2 is incorrect.
(SM9)
Continue Blinking Keep
16#003A
The setting of the communication type of COM2 is
incorrect. (SM9)
Continue Blinking Keep
16#0050
The memories in the latched special auxiliary relays
are abnormal.
Continue ON Keep
16#0051
The latched special data registers are abnormal.
Continue
ON
Keep
16#0052
The memories in the latched auxiliary relays are
abnormal.
Continue ON Keep
16#0053
The latched timers are abnormal.
Continue
ON
Keep
16#0054
The latched counters are abnormal.
Continue
ON
Keep
16#0055
The latched 32-bit counters are abnormal.
Continue
ON
Keep
16#0056
The memories in the latched timers are abnormal.
Continue
ON
Keep
16#0057
The memories in the latched counters are abnormal.
Continue
ON
Keep
16#0058
The memories in the latched 32-bit counters are
abnormal.
Continue ON Keep
16#0059
The latched data registers are abnormal.
Continue
ON
Keep
16#005A
The latched working registers are abnormal.
Continue
ON
Keep
16#005B
Abnormal SFC parameters
Continue
ON
Keep
16#005D
The CPU module does not detect a memory card.
(SM453
Continue Blinking Keep
16#005E
The memory card is initialized incorrectly. (SM453)
Continue
Blinking
Keep
16#005F
The data is read from the inexistent file in the memory
card, or the data is written into the inexistent file in the
memory card. (SM453)
Continue Blinking Keep
16#0060
The default folder can not be created in the CPU
module. (SM453)
Continue Blinking Keep
16#0061
The capacity of the memory card is not large enough.
(SM453)
Continue Blinking Keep
16#0062
The memory card is write protected. (SM453)
Continue
Blinking
Keep
16#0063
An error occurs when the data is written into the
memory card. (SM453)
Continue Blinking Keep
16#0064
The file in the memory card can not be read. (SM453)
Continue
Blinking
Keep
16#0065
The file in the memory card is a read-only file. (SM453)
Continue
Blinking
Keep
16#0066
An error occurs when the system is backupped.
Continue
Blinking
Keep
16#0067
The size of the PLC parameters restored exceeds the
size of the PLC parameters of the CPU module.
Continue Blinking Keep
16#0068
Corrupted symbol table
Stop
Blinking
Keep
16#0069
Corrutped EIP parameters
Stop
Blinking
Keep
16#1001
The PLC CPU cannot read/write data on the modules.
Continue
Keep
Blinking
16#1003
The mapped data between the PLC CPU and the
modules is not right.
Continue Keep Blinking
16#1400
An error occurs when the data is accessed through the
auxiliary processor. (SM9)
Stop Keep ON
16#1401
An error occurs when the data in the I/O module is
accessed. (SM9)
Stop Keep ON