Chapter 12 Troubleshooting
12-49
Error
code
Description Remedy
16#A031
The linear accumulation in
channel 3 exceeds the range.
To clear the linear accumulation, users need to set bit 1 in
CR84 to ON by means of FROM/TO.
16#A032
The scale set for channel
3exceeds the range.
Check the module parameter in HWCONFIG.
The scale set for channel 3 should be in the range of 0 to
32767.
16#A033
The number of cycles set for
channel 3 exceeds the range.
Check the module parameter in HWCONFIG.
The number of cycles set for channel 3 should be in the
range of 2 to 60.
16#A034
The comparison value set for
channel 3 exceeds the range.
Check the module parameter in HWCONFIG.
The comparison value set for channel 3 should be in the
range of -999999999 to 999999999.
16#A035
A limit value set for channel 3 is
incorrect.
Check the module parameter in HWCONFIG.
A limit value of set for channel 3 should be in the range of
-200000 to 200000.
16#A036
The interrupt number set for
channel 3 exceeds the range.
Check the module parameter in HWCONFIG.
The interrupt number set for channel 3 should be in the
range of 0 to 31.